4.2.11 Run Operations

CONFIGURATION SETTINGS

CHAPTER 4: FUNCTIONALITY

Entering a passcode at the Pass Code, Login screen will change the login indicated by an asterisk at the end of the line. The default passcode is “0”. You must be logged in as “Config” to be able to change the passcode. The green power LED will flash while logged in as configurator. The unit will stop any run relay when in configuration mode. The LM10 must be returned to user mode before beginning normal operations.

Once the passcode is changed, the PDU will retain it in memory and will automatically login when the CONFIG button is held/pressed upon plugging in the RJ11 connector or on power up. This is handy when using a hand held PDU for multiple relay program changes.

4.2.11 Run Operations

PATH: Configuration ØØØØØØØØØ Run Operations

Configuration

Run Operations „ Factory default

Run Operations

Run 1

Range: Run 1, Run 2, Stop

Input terminal 21 selects how the run command is controlled. If power is applied to the relay, then the network has run control. If not the hard-wired switches control. Note that a PDU logged in for configuration will disable run commands from both DeviceNet and hard- wired switches.

With DeviceNet fault enabled and scanner connections not yet established, switching to DeviceNet will cause the DeviceNet fault and stop any run condition of the LM10. Hard- wired Stop will always have priority. If stop terminal 3 is powered, the LM10 will not run.

4.2.12 Factory Default

PATH: Configuration ØØØØØØØØØØ Factory Default

Configuration Factory deflt „

Factory Default

No

Range: No, Yes

Select “Yes” to restore the factory values.