F9: Auxiliary Sense 1 / Run1-Run2 Time Delays

DEVICENET OPERATIONS

Value

CT Ratio

 

 

 

 

2

90 A sensor pack

 

 

 

 

3

75:5

 

 

 

 

4

100:5

 

 

 

 

5

120:5

 

 

 

 

6

150:5

 

 

 

 

7

200:5

 

 

 

 

8

225:5

 

 

 

 

CHAPTER 5: COMMUNICATIONS

Value

CT Ratio

10300:5

11400:5

12500:5

13600:5

14700:5

15800:5

F9: Auxiliary Sense 1 / Run1-Run2 Time Delays

Format: two bytes in format 0xHHLL, where LL is the auxiliary sense 1 time delay and HH is the Run1-Run2 time delay (Run1-Run2 time delay for revisions 1.40 and lower only)

Byte LL range: 0x00 to 0xFA (i.e. 0.0 to 25.0 seconds), where 0x00 is disabled

Byte LL multiplying factor: 0.1 (i.e. actual = byte LL in decimal 0.1 seconds)

Byte HH range: 0x00 to 0xB4 (i.e. 0 to 180 seconds)

F10: Auxiliary Sense 2 / Run2-Run1 Time Delays

Format: two bytes in format 0xHHLL, where LL is the auxiliary sense 2 time delay and HH is the Run2-Run1 time delay (Run2-Run1 time delay for revisions 1.40 and lower only)

Byte LL range: 0x00 to 0xFA (i.e. 0.0 to 25.0 seconds), where 0x00 is disabled

Byte LL multiplying factor: 0.1 (i.e. actual = byte LL in decimal 0.1 seconds)

Byte HH range: 0x00 to 0xB4 (i.e. 0 to 180 seconds)

F11: Auxiliary Relay Faults (16-bit bitmask)

Bitmask

Fault

 

 

---- ---- ---- ---1

Overcurrent

---- ---- ---- --1-

Reserved

---- ---- ---- -1--

Jam

 

 

---- ---- ---- 1---

Stall

 

 

---- ---- ---1 ----

Current unbalance

 

 

---- ---- --1- ----

Aux sense

 

 

---- ---- -1-- ----

Load loss

 

 

---- ---- 1--- ----

Reserved

 

 

---- ---1 ---- ----

Reserved

---- --1- ---- ----

DeviceNet

 

 

---- -1-- ---- ----

Voltage range

 

 

F12: Starter Type

Format: two bytes in format 0xHHLL, where LL is the motor type and HH is reserved Byte LL enumeration:

Value

Starter Type

 

 

0

FVNR (full voltage non-reversing)

 

 

1

FVR (full voltage reversing)

 

 

2

RV (reversing)

 

 

3

2S1W (two-speed one winding; Run-2, 4:1 ratio of Run-1)

 

 

4

2S2W (two-speed two winding; Run-2, 2:1 ratio of Run-1)

 

 

5

Custom

 

 

F13: CT Turns

Format: two bytes in format 0xHHLL, where LL is the number of CT turns and HH is reserved

5–58

LM10 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL

Page 64
Image 64
GE Motor Protection System F9 Auxiliary Sense 1 / Run1-Run2 Time Delays, F10 Auxiliary Sense 2 / Run2-Run1 Time Delays