FIGURE A–3: Ladder Logic for Setting Changes

CHAPTER A:

LM10 AND GE FANUC 90-30 WITH DEVICENET™

Word 17: Attribute (for example, 16#0200 [FLA Run1])

Word 18: Attribute (for example, 77 [77 0.1 amps])

FIGURE A–3: Ladder Logic for Setting Changes

Login (User Level) to the LM10:

The ladder logic for login (user level) to the LM10 using COMMREQ is shown below. Some key word settings to login (user level) to the LM10 from Slave 9 are shown below:

Word 11: Slave MAC ID setting (for example, 9)

Word 13: Login, User Level (for example, 16#33 [Login, User Level])

Word 14: Object Class to which the Request is directed (for example, 16#64)

Word 15: Instance of Object Class (for example, 1)

Word 17: Attribute (for example, 16#5000 [User])

Word 18: Passcode, value: 1

The changed parameters will be reflected in Reference View Table at address %R00256 and the FLA Run1 parameter will be displayed. Change the display format to unsigned decimal.

LM10 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL

A–15

Page 89
Image 89