Table A–7: Data to Get Motor Run Time

LM10 AND ALLEN-BRADLEY SLC500 VIA DEVICENET™

CHAPTER A:

Table A–7: Data to Get Motor Run Time

Address

Data (hex)

Description

 

 

 

 

 

 

N19:0

0101

TXID / Command

 

 

 

N19:1

0008

Port / Size

 

 

 

N19:2

0E09

Service / MAC ID (destination = 63)

 

 

 

N19:3

0064

Class

 

 

 

N19:4

0001

Instance

 

 

 

N19:5

0015

Attribute (Motor Run Time)

 

 

 

Table A–8: Data for Explicit Message Response, M1 Transferred to N20

Address

Data (hex)

Description

 

 

 

 

 

 

N20:0

0101

TXID / Command

 

 

 

N20:1

0002

Port / Size

 

 

 

N20:2

8E09

Service / MAC ID (Node = 09)

 

 

 

N20:3

Motor Run Time Value

Service Response Data

 

 

 

Refer to the DeviceNet Object Model of the LM10 relay for detail information on Class,

Instance, and Attribute.

A–24

LM10 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL

Page 98
Image 98
GE Motor Protection System, LM10 instruction manual Table A-7 Data to Get Motor Run Time, Instance, and Attribute