GE Motor Protection System, LM10 Attribute, Access, Name/Description, Data Type, Value

Models: LM10 Motor Protection System

1 106
Download 106 pages 52.19 Kb
Page 62
Image 62

DEVICENET OPERATIONS

 

CHAPTER 5: COMMUNICATIONS

 

 

 

 

 

 

 

Attribute

Access

Name/Description

Data Type

Value

 

 

 

 

 

 

 

0x09

Get/set

User setting, Run 2, stall

F4

Trip, Time

 

 

 

 

 

 

 

0x0A

Get/set

User setting, Run 1, unbalance

F5

Trip, Time

 

 

 

 

 

 

 

0x0B

Get/set

User setting, Run 2, unbalance

F5

Trip, Time

 

 

 

 

 

 

 

0x0C

Get/set

User setting, Run 1, load loss

F6

Trip, Time

 

 

 

 

 

 

 

0x0D

Get/set

User setting, Run 2, load loss

F6

Trip, Time

 

 

 

 

 

 

 

0x0E

Get/set

User setting, power transformers

F7

0 to 11

 

 

 

 

 

 

 

0x0F

Get/set

User setting, current transformers

F8

1 to 15

 

 

 

 

 

 

 

0x10

Get/set

User setting, auxiliary sense 1 timer

F9

0.1 (0 to 250)

 

 

 

 

 

 

 

0x11

Get/set

User setting, auxiliary sense 2 timer

F10

0.1 (0 to 250)

 

 

 

 

 

 

 

0x12

Get/set

User setting, auxiliary relay flags

F11

16 bits

 

 

 

 

 

 

 

0x15

Get

Motor run time hours

UINT

Hours

 

 

 

 

 

 

 

0x1A

Get/set

Configure passcode

UINT

Code (0)

 

 

 

 

 

 

 

0x24

Get/set

User setting, motor type

F12

Type 0 to 5

 

 

 

 

 

 

 

0x25

Get/set

User setting, loops through CT

F13

1 to 4

 

 

 

 

 

 

 

0x26

Get/set

Flags (Mrun, AutoRestart, O/V Volt

F14

16 bits

 

 

 

Enable, DNFault, 50 Hz)

 

 

 

 

 

 

 

 

 

0x2E

Call

Reset LM10*

N/A

---

 

0x1C

Call

Reset factory default user settings

N/A

---

 

 

 

 

 

 

 

0x2F

Get

Trip class

F17

---

 

 

 

 

 

 

 

0x30

Get

MAC ID

F18

---

 

 

 

 

 

 

 

0x31

Get

DeviceNet baud rate

F19

---

 

 

 

 

 

 

 

0x34

Get

Input switch status

F25

16 bits

 

 

 

 

 

 

 

0x38

Get

Remaining cool-down period

F26

16 bits

 

 

 

 

 

 

 

0x39

Get/set

Poll data group

F15

1 to 4

 

 

 

 

 

 

 

0x3A

Get/set

Run1-Run2 time delay

F16

0 to 600 sec.

 

 

 

 

 

 

 

0x3B

Get/set

Run2-Run1 time delay2

F16

0 to 600 sec.

 

0x40

History

Status (send data byte 0 for current, 1

F24

---

 

 

 

to 10 for history)

 

 

 

 

 

 

 

 

 

0x41

History

Phase A current

F23

0.1 A

 

 

 

 

 

 

 

0x42

History

Phase B current

F23

0.1 A

 

 

 

 

 

 

 

0x43

History

Phase C current

F23

0.1 A

 

 

 

 

 

 

 

0x44

History

Ground current

F23

0.1 A

 

 

 

 

 

 

 

0x45

History

Voltage

UINT

volts

 

 

 

 

 

 

 

0x46

History

Power factor

UINT

percent

 

 

 

 

 

 

 

0x47

History

Watts

F23

0.1 kW

 

 

 

 

 

 

 

0x48

History

Operating current

F23

0.1 A

 

 

 

 

 

 

 

0x49

History

Current unbalance

UINT

percent

 

 

 

 

 

 

 

0x50

Login

User

---

---

 

 

 

 

 

 

 

0x51

Login

Configuration

UINT

Passcode

 

 

 

 

 

 

 

0x52

Login

Calibration

UINT

Passcode

 

 

 

 

 

 

*This call function has the same result as pressing the Reset key on the PDU display Applies to revisions 1.50 and higher

The data type format codes for class code 0x64, instance 1 are shown below.

5–56

LM10 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL

Page 62
Image 62
GE Motor Protection System, LM10 instruction manual Attribute, Access, Name/Description, Data Type, Value