GE Motor Protection System A.2 LM10 and GE Fanuc 90-30 with DeviceNet, A.2.1 Overview

Models: LM10 Motor Protection System

1 106
Download 106 pages 52.19 Kb
Page 80
Image 80
A.2 LM10 and GE Fanuc 90-30 with DeviceNet™

LM10 AND GE FANUC 90-30 WITH DEVICENET™

CHAPTER A:

A.2 LM10 and GE Fanuc 90-30 with DeviceNet™

A.2.1 Overview

This section describes an example communications setup between the LM10 Motor

Protection System and the GE Fanuc 90-30 PLC via the DeviceNet protocol.

Explicit Messaging: for configuration and monitoring.

All the values mentioned in DeviceNet™ object model (voltage, current, power factor, trip class, FLA settings, etc.) can be monitored.

Polling Input/Output Connection: commands to the slave device and status from the slave device.

Data for assemblies #5 and #54. With polling, the Run1 and Run 2 contactors can be controlled. Note that only one relay output can be energized a time.

COS (Change of State) and Cyclic Input/Output Connection: for alarm/event notifications

Essentially, the COS/Cyclic connection is intended for monitoring the status of the Run1 and Run2 contactors.

A.2.2 GE Fanuc 90-30 PLC Hardware

The hardware for the setup example is indicated below:

Main Rack (Base 10 Slot or Base 5 Slot IC693CHS391/7)

Power Supply (IC693PWR XXX)

CPU (IC693CPU XXX) except CPU321 & CPU340

DeviceNet Master Module (IC693DNM200)

GE Fanuc Software: Cimpilcity ME version 4.00

DeviceNet Slave Module: GE Multilin LM10 Motor Protection System

A.2.3 Network Configuration

To connect the LM10 Motor Protection System to the DeviceNet™ master card (IC693DNM200), refer to chapter 2 of the Series 90-30 Programmable Controller manual (publication number GFK-2196).

A.2.4 Configuration Procedure

ZComplete the basic setup of the rack, power supply, and CPU.

ZAdd the DeviceNet™ master card (IC693DNM200) to any non-CPU slots 2 to 10.

ZStart the GE Fanuc Cimpilcity ME software.

ZAdd the slave device by right-clicking on the slot containing the DeviceNet™ master card, then click Add Slave.

A slave catalog will be displayed.