CHAPTER A:

LM10 AND ALLEN-BRADLEY SLC500 VIA DEVICENET™

0E (hex), 14 (decimal) = Get Attribute Single (read a single parameter)

10 (hex), 16 (decimal) = Set Attribute Single (write a single parameter)

32 (hex), 50 (decimal) = Get Attribute Multiple (read multiple parameters)

The MAC ID low byte is destination code 09.

The transaction body consists of the Class, Instance, Attribute, and Data bytes.

A.3.10 Ladder Logic

This discussion refers to the Ladder Logic diagrams shown on the following pages.

1.Rung 0000 to Rung 0004 are used to toggle the Bit B4/0 every 1 second; this is the input to BSL (Bit Shift Left).

2.For every 1 second toggle of B4/0, left-shift the N9:0 register.

3.The bits in the N9:0 register are used to enable Rungs 0007 to 0012.

4.Rung 0006 is used to reload the N9:0 register after overflow.

5.The COP function is used to copy the contains of the M1 file to a specific N register and transfer the values to the M0 file.

Table A–5: Data to Get Trip Class

Address

Data (hex)

Description

 

 

 

 

 

 

N31:0

0101

TXID / Command

 

 

 

N31:1

0008

Port / Size

 

 

 

N31:2

0E09

Service / MAC ID (Node 09)

 

 

 

N31:3

0064

Class

 

 

 

N31:4

0001

Instance

 

 

 

N31:5

002F

Attribute (Trip Class)

 

 

 

Table A–6: Data for Explicit Message Response, M1 Transferred to N20

Address

Data (hex)

Description

 

 

 

 

 

 

N32:0

0101

TXID / Command

 

 

 

N32:1

0002

Port / Size

 

 

 

N32:2

8E09

Service / MAC ID (Node = 09)

 

 

 

N32:3

Trip Class Value

Service Response Data

 

 

 

LM10 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL

A–23

Page 97
Image 97
GE LM10, Motor Protection System instruction manual A.3.10 Ladder Logic, Table A-5 Data to Get Trip Class