DEVICENET OPERATIONS

 

 

 

 

CHAPTER 5: COMMUNICATIONS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Data formats for device inputs

 

 

 

 

 

Bytes

Data Length

Name/Description

Data

 

Value

 

 

 

 

 

 

 

 

 

Format

 

 

 

 

 

22 bytes

1 word

 

Motor status

 

F22

---

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 word

 

Cause of trip

 

F20

---

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 word

 

Phase A current

UINT

0.1 A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 word

 

Phase B current

UINT

0.1 A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 word

 

Phase C current

UINT

0.1 A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 word

 

Ground current

UINT

0.1 A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 word

 

Voltage

 

UINT

volts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 word

 

Power factor

 

UINT

0.01

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 word

 

Power

 

UINT

0.1 kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 word

 

Average current

UINT

0.1 A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 word

 

Current unbalance

UINT

%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Assembly Object, Class Code 4, Instance 105

 

 

 

 

 

 

Attribute

 

Access

 

Name/Description

 

Data Type

 

Value

 

 

 

 

 

 

 

 

 

 

 

 

3

 

Get

Poll Data Group 4

 

 

 

see below

 

see below

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Data Formats for Device Inputs

 

 

 

 

 

Bytes

Data Length

Bytes

Name/Description

 

Data

 

Value

 

 

 

 

 

 

 

 

 

Format

 

 

 

7 bytes

1 byte

 

1

Motor status

F21

---

 

 

 

 

 

 

 

 

 

 

 

 

1 word

 

2 (Hi), 3 (Lo)

Phase A current

UINT

0.1 A

 

 

 

 

 

 

 

 

 

 

 

 

1 word

 

4 (Hi), 5 (Lo)

Phase B current

UINT

0.1 A

 

 

 

 

 

 

 

 

 

 

 

 

1 word

 

6 (Hi), 7 (Lo)

Phase C current

UINT

0.1 A

 

 

 

 

 

 

 

 

 

 

 

 

5.1.7Connection Object

The connection objects manage the characteristics of each communication connection. There are three instances of the connection object in the device. Explicit connection

(< 50ms response), input/output connection poll, (< 10ms response), and input/output connection Cos/Cyc (< 10ms response)

Connection Object, Class Code 5, Services:

Code

Name and Description of Services Available to this Object

 

 

0x05

Reset the connection - restart timer

 

 

0x0E

Get_Attribute_Single: Returns the contents of the given attribute.

 

 

0x10

Set_Attribute_Single: Sets the contents of the given attribute

 

 

Connection Object, Class Code 5, Attributes:

Attribute

Access

Name/Description

Data

Value

 

 

 

 

 

none

---

---

---

---

 

 

 

 

 

Connection Object, Class Code 5, Instance 1 (explicit message connection):

Attribute

Access

Name/Description

Data Type

Value

 

 

 

 

 

1

Get

State

BYTE

0x03

 

 

 

 

 

2

Get

Instance_type

BYTE

0x00, 0x01

 

 

 

 

 

3

Get

Export class trigger

BYTE

0x83

 

 

 

 

 

5–52

LM10 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL

Page 58
Image 58
GE Motor Protection System Connection Object, Class Code 5, Services, Connection Object, Class Code 5, Attributes