Gun Setup

The floor of the spray area: must be electrically conductive and grounded. Do not cover the floor with cardboard or any non-conductive material which would interrupt grounding continuity

All persons entering the spray area: must wear shoes having conductive soles such as leather, or wear personal grounding straps. Do not wear shoes with non-conductive soles such as rubber or plastic. If gloves are necessary, wear the conductive gloves supplied with the gun. If non-Graco gloves are worn, cut off fingers or palm area of gloves to ensure your hand contacts the grounded gun handle.

Flammable liquids in the spray area: must be kept in approved, grounded containers. Do not use plastic containers. Do not store more than the quantity needed for one shift.

Key to Figs. 12–15

Fig. 12

Operator is grounded through the

 

gun handle and conductive shoes.

 

 

Fig. 13

Object being sprayed is grounded

 

through contact with the hanger

 

and conveyor system.

Fig. 14

Gun is grounded through the

 

conductive air hose.

Fig. 15

Fluid supply line and source must

 

be grounded.