
6 Vent Clearances and Framing
A. Pipe Clearances to Combustibles
WARNING
Fire Risk. Explosion Risk.
Maintain vent clearance to combustibles as specified.
•Do not pack air space with insulation or other materials.
Failure to keep insulation or other materials away from vent pipe may cause fire.
Note: Heat shields MUST overlap by a minimum of
•SLP heat shield - designed to be used on a wall
•If wall thickness is less than
Heat
wall shield firestops
3 in. (76 mm) top clearance
1 in. (25 mm) clearance around vertical sections
Wall | 1/2 in. (13 mm) bottom |
clearance at wall | |
Shield | shield firestops |
Firestop |
|
1 in. (25 mm) | WALL |
clearance |
|
bottom and sides |
|
Figure 6.1 Horizontal venting clearances to combustible materials
B. Wall Penetration Framing
Combustible Wall Penetration
Whenever a combustible wall is penetrated, you must frame a hole for the wall shield firestop. The wall shield firestop maintains minimum clearances and prevents cold air infiltration.
•The opening must be framed on all four sides using the same size framing materials as those used in the wall construction.
•SLP pipe - A wall shield firestop must be placed on each side of an interior wall. A minimum
•See Section 8.L. for information for regarding the instal- lation of a horizontal termination cap.
Non-Combustible Wall Penetration
If the hole being penetrated is surrounded by noncom- bustible materials such as concrete, a hole with diameter one in. greater than the pipe is acceptable.
Whenever a
10 in. 10 in.
B
A*
A* | B |
38 in. | 37 in. |
*Shows center of vent framing hole for top venting. The center of the hole is one (1) inch (25.4 mm) above the center of the horizontal vent pipe.
Figure 6.2 Exterior Wall Hole
16 | Heat & Glo • Soho24B • |