Ground-Loop Heat Pump Applications

Table 1: Approximate Fluid Volume (U.S. gal. [L]) per 100' of Pipe

Fluid Volume (gal [liters] per 100’ [30 meters) Pipe)

Pipe

Size

Volume (gal) [liters]

 

 

 

 

1”

4.1 [15.3]

 

 

 

Copper

1.25”

6.4 [23.8]

 

 

 

 

2.5”

9.2 [34.3]

 

 

 

Rubber Hose

1”

3.9 [14.6]

 

 

 

 

3/4” IPS SDR11

2.8 [10.4]

 

 

 

 

1” iPS SDR11

4.5 [16.7]

 

 

 

 

1.25” IPS SDR11

8.0 [29.8]

 

 

 

 

Polyethylene

1.5” IPS SDR11

10.9

[40.7]

 

 

 

2” IPS SDR11

18.0

[67.0]

 

 

 

 

 

1.25” IPS SCH40

8.3 [30.9]

 

 

 

 

 

1.5” IPS SCH40

10.9

[40.7]

 

 

 

 

 

2” IPS SCH40

17.0

[63.4]

 

 

 

 

Unit Heat Exchanger

Typical

1.0

[3.8]

 

 

 

 

Flush Cart Tank

10” Dia x 3ft tall

10 [37.9]

[254mm x 91.4cm tall]

 

 

 

 

 

 

 

Figure 7: Loop Connection (Indoor Compressor Section)

 

 

NOTICE! Cabinet opening around loop piping (outdoor

 

 

compressor section) must be sealed to prevent entry of

 

 

rodents that could potentially damage unit wiring by chewing

 

 

on the insulation.

 

 

 

 

 

NOTICE! Outdoor compressor section may not be tilted

 

 

more than 5 degrees from level. Damage to the compressor

 

 

or stress on the loop piping could result if unit is tilted. A

 

 

concrete pad, anchor posts and/or soil compaction may be

 

 

required to avoid tilting as ground settles.

 

Table 2: Antifreeze Percentages by Volume

 

 

 

 

 

 

 

 

 

Type

Minimum Temperature for Low Temperature Protection

 

 

 

 

 

10°F [-12.2°C]

15°F [-9.4°C]

20°F [-6.7°C]

 

25°F [-3.9°C]

 

 

 

 

 

 

 

 

Methanol

25%

21%

16%

 

10%

100% USP food grade Propylene Glycol

38%

25%

22%

 

15%

Ethanol*

29%

25%

20%

 

14%

 

 

 

 

 

 

* Must not be denatured with any petroleum based product

w w w. h e a t c o n t o l l e r. c o m