CXM Control Start-up Operation
The control will not operate until all inputs and safety controls are checked for normal conditions. The compressor will have a 5 minute
Table 9b: Unit Operation
HTS | HSS | HSS | |
Variable Speed | Variable Speed | PSC Air Handler | |
| Air Handler | Air Handler |
|
G | Fan only | Fan only | Fan only |
|
|
|
|
G, Y or Y1 | Stage 1 heating1 | Stage 1 heating3 | Stage 1 heating5 |
G, Y1, Y2 | Stage 2 heating1 | Stage 2 heating3 | Stage 2 heating5 |
G, Y1, Y2, W | Stage 3 heating1 | Stage 3 heating3 | N/A |
G, W | Emergency heat | Emergency heat | Emergency heat |
|
|
|
|
G, Y or Y1, O | Stage 1 cooling2 | Stage 1 cooling4 | Cooling6 |
G, Y1, Y2, O | Stage 2 cooling2 | Stage 2 cooling4 | N/A |
1Stage 1 = 1st stage compressor, 1st stage fan operation Stage 2 = 2nd stage compressor, 2nd stage fan operation Stage 3 = 2nd stage compressor, auxiliary electric heat, 2nd
or 3rd stage fan operation (depending on fan settings)
2Stage 1 = 1st stage compressor, 1st stage fan operation, reversing valve
Stage 2 = 2nd stage compressor, 2nd stage fan operation, reversing valve
3Stage 1 = compressor, 1st stage fan operation Stage 2 = compressor, 2nd stage fan operation
Stage 3 = compressor, auxiliary electric heat, 2nd or 3rd stage fan operation (depending on fan settings)
4Stage 1 = compressor, 1st stage fan operation, reversing valve Stage 2 = compressor, 2nd stage fan operation, reversing valve
5Stage 1 = compressor, fan
Stage 2 = compressor, auxiliary electric heat, fan
6Cooling = compressor, fan, reversing valve