Heat Controller HTS SERIES SPLIT SYSTEM, HSS manual Unit Operating Conditions, Entering, Water

Models: HSS HTS SERIES SPLIT SYSTEM

1 48
Download 48 pages 27.01 Kb
Page 40
Image 40
Full Load Heating - without HWG active

H E AT C O N T R O L L E R , I N C . WAT E R - S O U R C E H E AT P U M P S

R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A

R e v. : 5 J u n e , 2 0 0 8

Unit Operating Conditions

Table 14d: Size 060 HTS Two-Stage R-410A Typical Unit Operating Pressures and Temperatures

Entering

Water

 

Full Load Cooling - without HWG active

 

 

Full Load Heating - without HWG active

 

Flow

 

 

 

 

 

 

 

 

 

 

 

 

Water

Suction

Discharge

Super-

Sub-

Water Temp

Air Temp

Suction

Discharge

Super-

Sub-

Water Temp

Air Temp

GPM/

Temp °F

Pressure

Pressure

Drop °F

Pressure

Pressure

Rise °F

ton

heat

cooling

Rise °F

heat

cooling

Drop °F

 

PSIG

PSIG

 

 

 

DB

PSIG

PSIG

 

 

 

DB

 

1.5

117-127

160-180

16-21

8-13

17.5-19.5

16-22

66-76

282-302

9-15

8-13

8-10

21-27

30

2.25

116-126

133-153

17-22

6-11

11.9-13.9

16-22

69-79

285-305

9-15

8-13

6-8

21-27

 

3

115-125

125-145

18-23

5-10

6.3-8.3

16-22

72-82

289-309

9-15

9-14

4-6

22-28

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5

126-136

228-248

8-13

8-13

19.8-21.8

20-26

95-105

318-338

9-15

12-17

11.3-13.3

27-33

50

2.25

124-134

212-232

11-16

6-11

14.2-16.2

20-26

100-110

321-341

9-15

12-17

8.5-10.5

28-34

 

3

123-133

195-215

14-19

5-10

8.5-10.5

20-26

105-115

324-344

9-15

12-17

5.7-7.7

30-36

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5

130-140

305-325

8-13

10-15

20.3-22.3

21-27

128-138

360-380

8-14

12-17

14-16

33-38

70

2.25

129-139

286-306

9-14

9-14

14.8-16.8

21-27

133-143

364-384

8-14

12-17

10.6-12.6

34-40

 

3

128-138

266-286

11-16

7-12

9.3-11.3

21-27

139-149

368-388

8-14

12-17

7.3-9.3

35-41

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5

133-143

398-418

8-13

10-15

19.4-21.4

20-26

173-183

407-427

8-14

13-18

18.2-20.2

42-50

90

2.25

132-142

376-396

8-13

9-14

14.1-16.1

20-26

177-187

411-431

8-14

13-18

13.9-15.9

43-51

 

3

132-142

354-374

8-13

7-12

8.8-10.8

20-26

182-192

415-435

8-14

14-19

9.6-11.6

44-52

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5

138-148

505-525

6-11

10-15

18.3-20.3

19-25

 

 

 

 

 

 

110

2.25

137-147

483-503

6-11

9-14

13.3-15.3

19-25

 

Operation Not Recommended

 

 

3

136-146

459-479

6-11

8-13

8.3-10.3

19-25

 

 

 

 

 

 

Table 15: R-22 HSS Typical Unit Operating Pressures and Temperatures

Entering

Water

 

Full Load Cooling - without HWG active

 

 

Full Load Heating - without HWG active

 

Flow

 

 

 

 

 

 

 

 

 

 

 

 

Water

Suction

Discharge

Super-

Sub-

Water Temp

Air Temp

Suction

Discharge

Super-

Sub-

Water Temp

Air Temp

GPM/

Temp °F

Pressure

Pressure

cooling

Drop °F

Pressure

Pressure

cooling

Rise °F

ton

heat

Rise *** °F

heat

Drop *** °F

 

PSIG

PSIG

 

****

 

DB

PSIG

PSIG

 

****

 

DB

 

1.5

61-70

100-117

12-18

12-22

21-24

21-26

34-39

163-183

5-10

5-9

7.6-8.4

14-20

30

2.3

62-71

92-109

12-18

12-22

13-16

21-26

37-42

165-185

5-10

5-9

4.8-5.6

16-22

 

3

62-71

88-104

12-18

12-22

6-11

21-26

38-44

167-186

5-10

5-9

3.4-4.2

16-22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5

79-85

145-170

10-15

9-16

20-23

20-25

51-58

175-202

9-12

8-12

10.8-11.9

23-29

50

2.3

75-83

130-155

10-15

9-16

12-15

20-25

53-62

178-206

9-12

8-12

6.7-8.1

24-30

 

3

72-82

125-150

10-15

9-16

8-12

20-25

55-65

180-208

9-12

8-12

5.1-5.9

25-31

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5

78-88

180-200

8-12

7-12

19-22

19-24

71-82

215-250

10-14

6-10

14.0-15.2

28-34

70

2.3

78-90

169-187

8-12

7-12

11-14

19-24

77-89

203-235

10-14

6-10

9.0-10.2

30-37

 

3

78-91

160-180

8-12

7-12

7-12

19-24

81-92

200-235

10-14

6-10

6.7-7.9

31-38

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5

79-82

230-272

8-10

7-11

18-21

17-23

 

 

 

 

 

 

90

2.3

80-93

215-248

8-10

7-11

10-14

17-23

 

Operation Not Recommended

 

 

3

80-93

208-240

8-10

7-11

6-11

17-23

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Based on Nominal 400 CFM per ton per circuit ariflow and 70°F EAT heating and 80/67°F cooling.

** Cooling air and water numbers can vary greatly with changes in humidity.

*** Water temperature difference based upon 1.5 - 3 GPM per ton of active circuit water flow.

**** Using liquid line pressure.

40

H e a t C o n t r o l l e r, I n c . Wa t e r - S o u r c e H e a t i n g a n d C o o l i n g S y s t e m s

Page 40
Image 40
Heat Controller HTS SERIES SPLIT SYSTEM Unit Operating Conditions, Entering, Water, Full Load Heating - without HWG active