Equipment Selection

The installation of geothermal heat pump units and all associated components, parts, and accessories which make up the installation shall be in accordance with the regulations of ALL authorities having jurisdiction and MUST conform to all applicable codes. It is the responsibility of the installing contractor to determine and comply with ALL applicable codes and regulations.

General

Proper indoor coil selection is critical to system efficiency. Using an older-model coil can affect efficiency and may not provide the customer with rated or advertised EER and COP. Coil design and technology have dramatically improved operating efficiency and capacity in the past 20 years. Homeowners using an older coil are not reaping these cost savings and comfort benefits. NEVER MATCH AN R-22

INDOOR COIL WITH AN R-410A COMPRESSOR SECTION.

Newer indoor coils have a larger surface area, enhanced fin design, and grooved tubing. These features provide a larger area for heat transfer, improving efficiency and expanding capacity. Typical older coils may only have one-third to one- half the face area of these redesigned coils.

Indoor Coil Selection - HTS GeoMax 2

HCI split system heat pumps are rated in the ARI directory with a specific indoor coil match. GeoMax 2 (HTS) models are rated with Carrier/Bryant FV4 or FE4 series variable speed air handlers as shown in Table 1a. Other brands of air handlers may attain the same ARI ratings providing that the specifications meet or exceed those listed in Table 1a AND Table 1b. An ECM motor and TXV is required. Cap tubes and fixed orifices are not acceptable. PSC fans may be used if matched to Table 1b, but will not meet ARI ratings. If using PSC fan, compressor section must be operated as a single stage unit (i.e. wired for either 1st stage or 2nd stage). Without the ability to vary the airflow, supply air temperatures may not be acceptable if the compressor is allowed to change stages when used with a PSC fan motor.

Table 1a: GeoMax 2 (HTS) Air Handler Matches for ARI Ratings

Compressor Section

024

036

048

060

 

 

 

 

 

Air Handler

003

005

006

006

Model FV4

 

 

 

 

 

 

 

 

 

Refrigerant

 

R-410A

 

 

 

 

 

Metering Device

 

TXV (required)

 

 

 

 

 

 

Air Coil

 

 

 

 

Type

Slope

A

A

A

Rows - Fins/in.

3 - 14.5

3 - 14.5

3 - 14.5

3 - 14.5

Face Area (sq. ft.)

3.46

5.93

7.42

7.42

 

 

 

 

 

Cabinet Configuration

Upflow/Downflow/Horizontal (Multipoise)

 

 

 

 

 

 

ECM Settings for

AC/HP size: 036

AC/HP size: 036

AC/HP size: 048

AC/HP size: 060

System Type:

System Type:

System Type:

System Type:

ARI Ratings

Comfort AC/HP

HP-Effic AC/HP

Comfort AC/HP

Comfort AC/HP

(FV4 Fan Coil)

CFM Adjust: Nom

CFM Adjust: High

CFM Adjust: High

CFM Adjust: High

 

 

 

 

 

 

Fan Motor Type - HP

ECM - 1/2

ECM - 1/2

ECM - 3/4

ECM - 3/4

 

 

 

 

 