T h e Q u a l i t y L e a d e r i n C o n d i t i o n i n g A i r

R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A

R e v. : 5 J u n e , 2 0 0 8

Unit Starting and Operating Conditions

Operating Limits

2. Voltage utilization range complies with ARI

Environment – “Indoor” compressor section is designed for

Standard 110.

indoor installation only. Never install “indoor” compressor

 

section in areas subject to freezing or where humidity levels

Determination of operating limits is dependent primarily upon

could cause cabinet condensation (such as unconditioned

three factors: 1) return air temperature. 2) water temperature,

spaces subject to 100% outside air). “Outdoor” unit is designed

and 3) ambient temperature. When any one of these factors

for conditions where ambient air is below freezing (see Table

is at minimum or maximum levels, the other two factors

11).

should be at normal levels to insure proper unit operation.

Power Supply – A voltage variation of +/– 10% of nameplate

 

utilization voltage is acceptable.

Extreme variations in temperature and humidity and/or

Starting Conditions

corrosive water or air will adversely affect unit performance,

reliability, and service life.

Consult Table 11 for the particular model. Starting conditions

 

vary depending upon model and are based upon the

 

following notes:

 

Notes:

1.Conditions in Table 11 are not normal or continuous operating conditions. Minimum/maximum limits are start- up conditions to bring the building space up to occupancy temperatures. Units are not designed to operate under these conditions on a regular basis.

Table 11: Unit Operation

Operating Limits

HTS/HSS

PDW

Cooling

Heating

Cooling

Heating

 

 

 

 

 

 

Air Limits

 

 

 

 

 

 

 

 

 

Min. ambient air, DB

45°F [7°C]

39°F [4°C]

-10°F [-23°C]

-10°F [-23°C]

 

 

 

 

 

Rated ambient air, DB

80.6°F [27°C]

68°F [20°C]

80.6°F [27°C]

68°F [20°C]

 

 

 

 

 

Max. ambient air, DB

110°F [43°C]

85°F [29°C]

110°F [43°C]

85°F [29°C]

 

 

 

 

 

Min. entering air, DB/WB

50°F [10°C]

40°F [4.5°C]

50°F [10°C]

50°F [10°C]

 

 

 

 

 

Rated entering air, DB/WB

80.6/66.2°F [27/19°C]

68°F [20°C]

80.6/66.2°F [27/19°C]

68°F [20°C]

 

 

 

 

 

Max. entering air, DB/WB

110/83°F [43/28°C]

80°F [27°C]

110/83°F [43/28°C]

80°F [27°C]

 

 

 

 

 

Water Limits

 

 

 

 

 

 

 

 

 

Min. entering water

30°F [-1°C]

20°F [-6.7°C]

30°F [-1°C]

20°F [-6.7°C]

 

 

 

 

 

Normal entering water

50-110°F [10-43°C]

30-70°F [-1 to 21°C]

50-110°F [10-43°C]

30-70°F [-1 to 21°C]

 

 

 

 

 

Max. entering water

120°F [49°C]

90°F [32°C]

120°F [49°C]

90°F [32°C]

 

 

 

 

Normal water flow

1.5 to 3.0 gpm/ton

1.5 to 3.0 gpm/ton

 

 

 

 

2.0 to 3.9 l/m per kW

2.0 to 3.9 l/m per kW

 

 

 

 

 

 

w w w. h e a t c o n t o l l e r. c o m

35

Page 35
Image 35