Heat Controller HTS SERIES SPLIT SYSTEM, HSS manual Water Quality Standards, Corrosion Prevention

Models: HSS HTS SERIES SPLIT SYSTEM

1 48
Download 48 pages 27.01 Kb
Page 16
Image 16
Water Quality Standards

H E AT C O N T R O L L E R , I N C . WAT E R - S O U R C E H E AT P U M P S

R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A

R e v. : 5 J u n e , 2 0 0 8

Water Quality Standards

Table 3: Water Quality Standards

Water Quality

HX

Closed

Open Loop and Recirculating Well

Parameter

Material

Recirculating

 

Scaling Potential - Primary Measurement

 

Above the given limits, scaling is likely to occur. Scaling indexes should be calculated using the limits below.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pH/Calcium Hardness

All

 

-

 

pH < 7.5 and Ca Hardness <100ppm

 

Method

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Index Limits for Probable Scaling Situations - (Operation outside these limits is not recommended)

 

 

 

 

 

Scaling indexes should be calculated at 150°F [66°C] for direct use and HWG applications,

 

 

 

and at 90°F [32°C] for indirect HX use. A monitoring plan should be implemented.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ryznar

All

 

 

-

 

6.0 - 7.5

 

 

 

 

Stability Index

 

 

 

 

If >7.5 minimize steel pipe use.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Langelier

All

 

-

 

 

-0.5 to +0.5

 

 

 

 

 

 

If <-0.5 minimize steel pipe use. Based upon 150°F [66°C] HWG and

 

Saturation Index

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Direct well, 85°F [29°C] Indirect Well HX

 

 

 

 

 

 

 

 

 

Iron Fouling

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Iron Fe 2+ (Ferrous)

All

 

 

-

 

 

<0.2 ppm (Ferrous)

 

 

 

(Bacterial Iron potential)

 

 

 

If Fe2+ (ferrous)>0.2 ppm with pH 6 - 8, O2<5 ppm check for iron bacteria

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Iron Fouling

All

 

-

 

 

<0.5 ppm of Oxygen

 

 

 

 

 

 

Above this level deposition will occur.

 

 

 

 

 

 

 

 

 

 

 

Corrosion Prevention

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6 - 8.5

 

6 - 8.5

 

 

 

 

pH

All

 

 

 

 

 

 

 

 

 

 

Monitor/treat as

Minimize steel pipe below 7 and no open tanks with pH <8

 

 

 

 

 

needed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-

 

 

<0.5 ppm

 

 

 

Hydrogen Sulfide (H2S)

All

 

 

 

At H2S>0.2 ppm, avoid use of copper and copper nickel piping or HX's.

 

 

 

 

 

Rotten egg smell appears at 0.5 ppm level.

 

 

 

 

 

 

Copper alloy (bronze or brass) cast components are OK to <0.5 ppm.

 

 

 

 

 

 

 

 

 

 

 

 

 

Ammonia ion

 

 

-

 

 

 

 

 

 

 

as hydroxide, chloride,

All

 

 

 

 

 

<0.5 ppm

 

 

 

nitrate and sulfate

 

 

 

 

 

 

 

 

 

 

 

compounds

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum Allowable at maximum water temperature.

 

 

 

 

 

 

 

50°F (10°C)

 

75°F (24°C)

 

100ϒF (38ϒC)

 

Maximum

Copper

 

 

-

<20ppm

 

NR

 

NR

 

 

CuproNickel

 

-

<150 ppm

 

NR

 

NR

 

Chloride Levels

 

 

 

 

304 SS

 

-

<400 ppm

 

<250 ppm

 

<150 ppm

 

 

 

 

 

 

 

316 SS

 

-

<1000 ppm

 

<550 ppm

 

< 375 ppm

 

 

Titanium

 

-

>1000 ppm

 

>550 ppm

 

>375 ppm

 

Erosion and Clogging

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<10 ppm of particles

 

 

 

 

 

 

 

 

 

 

 

and a maximum

<10 ppm (<1 ppm "sandfree" for reinjection) of particlesand a maximum

 

Particulate Size and

All

 

 

velocity of 6 fps [1.8 m/s].

velocity of 6 fps [1.8 m/s]. Filtered for maximum 800 micron [800mm,

 

Erosion

 

 

 

Filtered for maximum

20 mesh] size.Any particulate that is not removed can potentially

 

 

 

 

800 micron [800mm,

 

 

 

 

 

clog components.

 

 

 

 

 

 

 

20 mesh] size.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Notes:

 

 

 

 

 

 

 

 

Rev.: 03/28/08S

 

 

 

 

 

 

 

 

 

 

 

Closed Recirculating system is identified by a closed pressurized piping system.

Recirculating open wells should observe the open recirculating design considerations.

NR - Application not recommended.

"-" No design Maximum.

16

H e a t C o n t r o l l e r, I n c . Wa t e r - S o u r c e H e a t i n g a n d C o o l i n g S y s t e m s

Page 16
Image 16
Heat Controller HTS SERIES SPLIT SYSTEM, HSS manual Water Quality Standards, Corrosion Prevention, Iron Fouling