BACnet/IP MODULE

Object Examples

In the first example, we see the CO2 gas sensor input for a 301D2 Vulcain network device:

Name : “301D2 CO2 AD:14.CO2”

Value : 600

Units : PPM

Object : 1.AI2*

Description : Analog Input

*1 is the 301C unique device instance, AI is the object type and 2 is the unique instance of the object in this device. We identify this object as “Analog Input 2 of BACnet device 1”.

In this example, we can see the output status for relay 2 of the same Vulcain network device, but with a different device display label:

Name : “Floor 01 Sensor 02 .rel2”

Value : OFF

Units :

Object : 1.BO4*

Description : Binary Output

*We identify this object as “Binary Output 4 of BACnet device 1”.

Example 3 where we can see the first 24V output status of a 301EM Vulcain network device.

Name : “301EM CO AD:25.out1”

Value : OFF

Units :

Object : 1.BV1

Description : Binary Value*

*We identify this object as “Binary Value 1 of BACnet device 1”.