BACnet/IP MODULE
Binary Output
The Binary Output object type defines a standardized object whose properties represent the externally visible characteristics of a binary output. A "binary output" is a physical device or hardware output that can be in only one of two distinct states, such as a relay or a switchable power output.
Supported properties for the Binary Output object type are : Object_Identifier, Object_Name, Object_Type, Status_Flags, Event_State, Reliability, Present_Value, Polarity, Inactive_Text, Active_Text, Priority_Array, Relinquish_Default and Out_of_Service.
Binary Value
The Binary Value object type defines a standardized object whose properties represent the externally visible characteristics of a binary value. A "binary value" is a control system parameter residing in the memory of the BACnet Device.
Supported properties for the Binary Value object type are : Object_Identifier, Object_Name, Object_Type, Status_Flags, Event_State, Reliability, Present_Value, Inactive_Text, Active_Text, Priority_Array, and Relinquish_Default.
Device
The Device object type defines a standardized object whose properties represent the externally visible characteristics of a BACnet Device. There is only one Device object to represent the BACnet Module.
Supported properties for the Device object are : Object_Identifier, Object_Name, Object_Type, System_Status, Vendor_Name, Vendor_Identifier, Model_Name, Firmware_Revision, Application_Software_Version, Protocol_Version, Protocol_Revision, Protocol_Services_Supported, Protocol_Object_Types_Supported, Object_List, Max_APDU_Length_Accepted, Segmentation_Supported, APDU_Timeout, Number_Of_APDU_Retries, Device_Address_Binding, Database_Revision, Local_Time, Local_Date, UTC_Offset, Daylight_Savings_Status and Out_of_Service.
301C User Manual | 93 | |