Event Menu
Conditions
Conditions are the parameters that define what makes an Event true. Each condition is defined by four elements and can be combined with other conditions to provide greater flexibility. A condition, as in the example provided below, defines:
IF at least 1/3 of group 36 detects concentrations greater than 2.01% of specified gas AND all of group 03 detects a concentration greater than 2.99% of gas, then the specified action (Actions were set at the first Event screen) for that Event will be triggered.
Since the display screens offer limited space, scroll left and right to view and edit further information.
Condition programming screens
| 3. Events | 001 |
1/3 | Gr036 |
|
> | 2.01% | AND |
| 3. Events 001 |
all | Gr003 |
AND > | 2.99% |
The portion of the Events condition screen that is within the brackets is divided into four editable list fields:
45
7/10 | Honeywell |