System Programming
Event Menu
The bottom left portion contains the logic, or operator, quantifier that determines how conditions are calculated. Options available in this field are:
Operator
Symbol
Meaning
---No operator
=Equal to
<= | Equal to or smaller than |
<Smaller than
>= | Equal to or larger than |
>Larger than
!= | Not equal to |
max
When the maximum value is reached, an action is triggered. It will not be deactivated until levels fall below minimum value
When concentrations fall below minimum value, an action is
min triggered. It will not be deactivated until concentrations rise above set maximum value
The top right portion contains the source, which defines what device or group of devices the Event will be based on. The list provides the following options:
GrAll: Includes all transmitters (see note)
Gr_ _ _: Includes only the devices in the specified group (see note)
Tx000: | Includes only the specified transmitter (connected to the con- |
| troller) |
Clock: | Includes only information gathered between the specified |
| times. Selecting clock sets a condition that is applied only |
| between the start and end time frame. It is possible to set |
| one condition screen to specific parameters and the second |
| to clock, which means that the specified condition will trigger |
| an event only if it occurs during the set time period. |
Note: Clicking on the magnifying glass to the right of a Group number on the display opens a view of the Group for consultation or editing. Press Esc to close the group view and return to the Event condition screen.
301C User Manual | 47 | |