System Programming
Network Menu
Remote Calibration
The network menu also offers a Calibration option for use with devices that support network calibration.
7. Network
Statistics
Calibration
The Calibration screen contains four (4) lines of information:
Calib |
| 007 |
| S301M |
|
| |||
Status: | Normal | |||
Set Zero |
|
| ||
Set Span | 246 | PPM |
Line 1: Indicates the mode (Calib, meaning calibration), the (Modbus) address of the device to calibrate (001) and the type of device to calibrate (301D2)
Line 2: Indicates the status (Normal or In calib…) of the specified device
Line 3: Displays the function to perform (Set Zero)
Line 4: Displays the function to perform (Set Span) and the span gas concentration value (246 ppm)
5.On the first line, scroll to the device address and press Enter
6.Scroll through the devices to display the desired device* and press Enter to select.
7.The second line displays the device’s status
8.Scroll to select the desired function, Set Zero to set the device's zero, and press Enter to select.
9.Upon pressing Set Zero, the controller requests confirmation.
|
| Calib 007 |
| S301M |
|
| Status: | Normal | |
|
| Set Zero |
|
|
|
|
|
| |
|
| Set Span | 246 | PPM |
*The device must be configured in the 301C’s database in order to be included in the device addresses displayed on screen.
301C User Manual | 63 | |