System Programming
Tests Menu
Test Sequence
When test sequence is selected from the main Tests menu, the controller will display the Test sequence screen.
Test sequence
Relays activated
Any key to continue
Esc to quit
If Esc is pressed on the keypad, the main Tests menu screen will be displayed. However, to perform system tests, press any key to proceed to the first test screen.
Test sequence
BUZZER activated
Any key to continue
Esc to quit
This screen tests each component individually and will advance only to the next component when a key is pressed. This option will display 13 screens. Screens 1, 2 and 3 test Relays, BUZZER and LEDs.
The following six screens prompt the user to press the keypad buttons, in turn: left, right, up, down, Silence, Enter and Esc. The system will not advance until a key is pressed.
Test sequence
Press ‘left’
Esc to quit