System Programming
Configuration
Parameters
The “parameters” function allows one transmitter’s configuration to be copied to another or one event’s parameters to be copied to another event. This allows several devices that share identical or similar parameters to be quickly configured.
5. Copy
TxInfo to TxInfo Event to Event
The options within this screen are:
Tx Info to Tx Info copies transmitter parameters from one device to another.
Event to Event copies parameters from Event to Event.
The process is identical for both options:
•Select source, (the data to be copied) using the up/down keypad arrows and press Enter.
•When the transmitter address is flashing, use the up/down keypad buttons to search for the desired device address.
•Press Enter to select the new address
•Select the target address (where the data is to be copied to) in exactly the same way as source
•Select COPY and press Enter. The parameters have been copied.
TxInfo to TxInfo source tx001 target tx113
COPY
Event to Event source #001 target #013
COPY