BACnet/IP MODULE

Honeywell Products and BACnet Objects

Object Names

Object names are constructed in two parts, as follows:

Part one: The device display label (product name) for the network in which the object resides. This value is editable only when using the 301C controller.

Part two: Unique tag label among all the objects for the same device.

Ex : “301D2 CO2 AD:14.CO2” where ‘301D2 CO2 AD:14’ is the device display label and ‘CO2’ is the unique tag label that identifies the object as a CO2 sensor.

Vulcain Object Tag Labels

Table 1:

Tag Labels

Description

Object

Type

 

 

 

 

 

‘Gas label’

Gas sensor

AI

.Alrm

Simple alarm level

AV

Amin /Amax

Alarm level A and hysteresis

AV

Bmin /Bmax

Alarm level B and hysteresis

AV

Cmin /Cmax

Alarm level C and hysteresis

AV

relx

Relay output X (1 to 8)

BO

buzz

Buzzer output

BO

.outx

Output X (1 to 3)

BO or BV

.AIx

Analog input X (1 to 16)

AI

.BIx

Binary Input X (1 to 12)

BI

.RH

Relative Humidity sensor

AI

.Temp

Temperature sensor

AI

 

 

 