BACnet/IP MODULE
Honeywell Products and BACnet Objects
Object Names
Object names are constructed in two parts, as follows:
Part one: The device display label (product name) for the network in which the object resides. This value is editable only when using the 301C controller.
Part two: Unique tag label among all the objects for the same device.
Ex : “301D2 CO2 AD:14.CO2” where ‘301D2 CO2 AD:14’ is the device display label and ‘CO2’ is the unique tag label that identifies the object as a CO2 sensor.
Vulcain Object Tag Labels
Table 1:
Tag Labels | Description | Object | |
Type | |||
|
| ||
|
|
| |
‘Gas label’ | Gas sensor | AI | |
.Alrm | Simple alarm level | AV | |
Amin /Amax | Alarm level A and hysteresis | AV | |
Bmin /Bmax | Alarm level B and hysteresis | AV | |
Cmin /Cmax | Alarm level C and hysteresis | AV | |
relx | Relay output X (1 to 8) | BO | |
buzz | Buzzer output | BO | |
.outx | Output X (1 to 3) | BO or BV | |
.AIx | Analog input X (1 to 16) | AI | |
.BIx | Binary Input X (1 to 12) | BI | |
.RH | Relative Humidity sensor | AI | |
.Temp | Temperature sensor | AI | |
|
|
|