Bacnet Menu
The Foreign Device Registration (FDR) allows users to enable the FDR and to set a specific Time To Live (in seconds).
9. BACNet -ForeignDevReg:dis-
Enable FDR TTL: 43200 sec
A Foreign Device is a BACNet device that has an IP subnet address different from those on the BACNet/IP network it seeks to join.
The TTL
The BBMD Info screen lets users specify the address for the BBMD to which the device will try to connect (or register).
9. BACNet
IP: 192.168. 1.100
Port: 0xBAC0
For more information on this subject, please consult the ASHRAE standard number