Bacnet Menu

The Foreign Device Registration (FDR) allows users to enable the FDR and to set a specific Time To Live (in seconds).

9. BACNet -ForeignDevReg:dis-

Enable FDR TTL: 43200 sec

A Foreign Device is a BACNet device that has an IP subnet address different from those on the BACNet/IP network it seeks to join.

The TTL (Time-To-Live) parameter is the registration duration supplied to the BBMD at the time of registration. Devices must re-register within this specified interval to remain connected.

The BBMD Info screen lets users specify the address for the BBMD to which the device will try to connect (or register).

9. BACNet -BBMD Info-

IP: 192.168. 1.100

Port: 0xBAC0

For more information on this subject, please consult the ASHRAE standard number 135-2001, Annex J, section J5.