Gen Run Hold Time

The XW Auto Gen Start Menu

Gen Run Hold Time

Full name

Generator Run Signal Hold Time

 

 

Purpose

“Gen Run Hold Time” specifies the length of time the generator run

 

signal (or B+ or hour meter signal) must be active before the XW Auto

 

Generator Start considers the generator to be running and cranking can be

 

stopped.

 

 

 

Some generators assert their run signal when they are being cranked, but

 

before they have started. They also have varying delays from when

 

cranking begins or ends to when the run signal is asserted or unasserted.

 

The Run Hold Time is designed to accommodate these generators.

 

Values

 

Default

 

 

 

 

 

 

 

0.0s to 20.0s (increments of 0.5s)

 

0.5s

 

 

 

 

Considerations

This setting is automatically configured when a “Gen Type” is selected

 

for the generator. Manually change this setting only on the advice of the

 

generator manufacturer or authorized service personnel.

Crank Delay

 

 

 

Purpose

“Crank Delay” specifies the delay time from when the preheat relay is de-

 

energized to when the Start Relay is energized (and cranking the starter

 

motor). This is also referred to as the preheat-to-crank delay.

Values

0s to 250s

Default

1s

Considerations

This setting is automatically configured when a “Gen Type” is selected

 

for the generator. Manually change this setting only on the advice of the

 

generator manufacturer or authorized service personnel.

Crank Time

Purpose

“Crank Time” specifies the maximum length of time the Start relay is

 

engaged (and cranking the starter motor) for the first attempt to start the

 

generator.

 

 

 

Values

 

Default

 

 

 

 

 

 

 

0s to 250s (increments of 1s)

 

30s

 

 

 

 

Considerations

This setting is automatically configured when a “Gen Type” is selected

 

for the generator. Manually change this setting only on the advice of the

 

generator manufacturer or authorized service personnel.