Troubleshooting
Table | XW Auto Generator Start Warning Messages(Continued) | |||
|
|
|
|
|
Warning |
| Self- |
|
|
Number | Message | clearing? | Cause | Action |
|
|
|
|
|
W203 | Manual Off: Max | No | The generator has run for | Acknowledge the warning. |
| generator run time |
| its maximum allowable | Return the XW Auto |
| reached. Reset |
| time. The XW Auto | Generator Start to the |
| GenMode. |
| Generator Start has stopped | desired GenMode |
|
|
| the generator and changed | [Automatic or ManualOn]. |
|
|
| the GenMode to | Ensure generator has fuel |
|
|
| [ManualOff]. | and is supplying the |
|
|
|
| required power for battery |
|
|
|
| charging and loads. |
|
|
|
|
|
W205 | Generator started | Yes | The generator was started, | Check your generator. Stop |
| by its switch. Use |
| but not by the XW Auto | it using the switch or |
| its switch to stop. |
| Generator Start. | control panel on the |
|
|
|
| generator. |
|
|
|
|
|
W206 | Mismatched | No | You have set a start trigger, | Acknowledge warning and |
| triggers. Enable |
| but not a corresponding | set a stop trigger. |
| stop trigger or |
| stop trigger. |
|
| disable start trigger. |
|
|
|
|
|
|
|
|
W207 | Mismatched | No | You have set a stop trigger, | Acknowledge warning and |
| triggers. Enable |
| but not a corresponding | set a start trigger. |
| start trigger or |
| start trigger. |
|
| disable stop trigger. |
|
|
|
|
|
|
|
|
W208 | Automatic start and | No | You are attempting to enter | Acknowledge warning and |
| stop triggers not |
| Automatic Mode without | set start and stop triggers. |
| enabled. Configure |
| setting triggers. |
|
| triggers. |
|
|
|
|
|
|
|
|
W209 | Gen external stop. | Yes | The generator has stopped, | Check the generator’s fuel |
| Start gen via its |
| but not by the XW Auto | level and mechanical |
| control panel. |
| Generator Start. The | condition, then start the |
|
|
| generator may have run out | generator manually (using |
|
|
| of gas, or may have been | the switch or control panel |
|
|
| shut off by a switch on the | on the generator) to clear |
|
|
| generator. | the warning. |
|
|
|
|
|