Troubleshooting

Table 5-1

XW Auto Generator Start Warning Messages(Continued)

 

 

 

 

 

Warning

 

Self-

 

 

Number

Message

clearing?

Cause

Action

 

 

 

 

 

W203

Manual Off: Max

No

The generator has run for

Acknowledge the warning.

 

generator run time

 

its maximum allowable

Return the XW Auto

 

reached. Reset

 

time. The XW Auto

Generator Start to the

 

GenMode.

 

Generator Start has stopped

desired GenMode

 

 

 

the generator and changed

[Automatic or ManualOn].

 

 

 

the GenMode to

Ensure generator has fuel

 

 

 

[ManualOff].

and is supplying the

 

 

 

 

required power for battery

 

 

 

 

charging and loads.

 

 

 

 

 

W205

Generator started

Yes

The generator was started,

Check your generator. Stop

 

by its switch. Use

 

but not by the XW Auto

it using the switch or

 

its switch to stop.

 

Generator Start.

control panel on the

 

 

 

 

generator.

 

 

 

 

 

W206

Mismatched

No

You have set a start trigger,

Acknowledge warning and

 

triggers. Enable

 

but not a corresponding

set a stop trigger.

 

stop trigger or

 

stop trigger.

 

 

disable start trigger.

 

 

 

 

 

 

 

 

W207

Mismatched

No

You have set a stop trigger,

Acknowledge warning and

 

triggers. Enable

 

but not a corresponding

set a start trigger.

 

start trigger or

 

start trigger.

 

 

disable stop trigger.

 

 

 

 

 

 

 

 

W208

Automatic start and

No

You are attempting to enter

Acknowledge warning and

 

stop triggers not

 

Automatic Mode without

set start and stop triggers.

 

enabled. Configure

 

setting triggers.

 

 

triggers.

 

 

 

 

 

 

 

 

W209

Gen external stop.

Yes

The generator has stopped,

Check the generator’s fuel

 

Start gen via its

 

but not by the XW Auto

level and mechanical

 

control panel.

 

Generator Start. The

condition, then start the

 

 

 

generator may have run out

generator manually (using

 

 

 

of gas, or may have been

the switch or control panel

 

 

 

shut off by a switch on the

on the generator) to clear

 

 

 

generator.

the warning.

 

 

 

 

 