Xantrex Technology XW manual 17 Type 13 Connection Diagram

Models: XW

1 124
Download 124 pages 55.26 Kb
Page 43
Image 43
Figure 2-17Type 13 Connection Diagram

Installing the XW Automatic Generator Start

Type 13

Type 13 is a three-wire PulseStop configuration that uses relay 3 to provide the preheat signal for PowerTech’s Diesel generators. With this generator type, there will be a delay between the generator turning off and the XW Auto Generator Start recognizing that the generator is off.

XW AGS Harness Wires

Generator Wires

Relay 1

Relay 2

Relay 3

12

13

14

16

17

18

19

20

 

 

 

 

GENERATOR RUN SIGNAL

 

 

 

 

 

 

 

 

GENERATOR BATTERY NEGATIVE(–)

 

 

 

5A fuse

 

 

 

STOP/PREHEAT

 

 

 

 

 

 

 

 

 

 

 

5A fuse

START

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5A fuse FUEL PRIME (PREHEAT)

12V GENERATOR BATTERY+

For additional information, see “Circuit Limitations” on page 2–5.

Figure 2-17Type 13 Connection Diagram

Table 2-16Type 13 Relay and Timing Preset Configurations

Relay Function

Preset Configuration Setting

 

 

Relay 1 mode

PulseStop

 

 

Relay 3 mode

Preheat

 

 

Gen Run signal hold time

5 s

 

 

Preheat time

15 s

 

 

Preheat to crank delay

2 s

 

 

Crank time

15 s

 

 

Crank retry time

15 s

 

 

Gen Cool Down

30 s

 

 

Shutdown bypass time

0 s

 

 

Start tries

3

 

 

975-0307-01-01

2–21

Page 43