Relay Timing

RunMode

For generators with RunMode starting types (Types 7 and 8):

Relay 1 (RunStop relay) can be used for two-wire configured generators.

Relay 1 (RunStop) and Relay 2 (Start) can be used with a common ground for three-wire configured generators.

The Preheat will never overlap the Crank Time.

The “Delay” refers to the “Preheat to Crank Delay” and may be zero.

Cranking will cease when the generator run signal goes high for the specified hold time or when the crank time has elapsed.

Figure C-1RunMode Timing Diagram

C–2

975-0307-01-01

Page 110
Image 110
Xantrex Technology XW manual Figure C-1RunMode Timing Diagram