The XW Auto Gen Start Menu

Starter Cool Down

Purpose

The Starter Cool Down setting allows an interval to be set between start

 

attempts if the generator fails to start on the first attempt. This time period

 

allows the start motor to cool sufficiently before the XW Auto Generator

 

Start signals it to begin cranking again.

 

 

 

Values

 

Default

 

 

 

 

 

 

 

1s to 250s (increments of 1s)

 

60s

 

 

 

 

When to use

This setting is automatically configured when a “Gen Type” is selected

 

for the generator. Customize the “Starter Cool Down” trigger on the

 

advice of the generator manufacturer or authorized service personnel.

Gen Cool Down

Purpose

The Gen Cool Down setting allows an interval to be set between a

 

generator stop trigger occurring and the AGS actually stopping the

 

generator. This setting is used in XW system to unload the generator

 

before the AGS shuts it down. When a stop trigger occurs, the AGS enters

 

a Generator cool down state where it continues to run the generator for the

 

specified time period. At the same time the XW inverter/charger will

 

disconnect the generator when it detects the AGS in Generator Cool

 

Down, allowing the generator operate unloaded and cool down before it is

 

shut down.

 

 

 

This helps improves reliability of the generator by reducing temperature

 

peaking due to abrupt shut down of a loaded generator. It also reduces the

 

probability of the generator backfiring that typically happens when the

 

generator is abruptly shutdown while under heavy load. Gen Cool Down

 

applies to all stop triggers namely Stop V, Stop Load, Stop float, Stop

 

Absorb, Stop Load, and Manual Off.

 

 

 

Values

 

Default

 

 

 

 

 

 

 

1s to 90s (increments of 1s)

 

30s

 

 

 

 

When to use

This setting is automatically configured when a “Gen Type” is selected

 

for the generator. Customize the “Gen Cool Down” trigger on the advice

 

of the generator manufacturer or authorized service personnel.