Installation
Type 10
Type 10 is a StartStop mode configuration with no preheat signal or shutdown bypass functionality.
XW AGS Harness Wires | Generator Wires |
Relay 1
Relay 2
12
13
14
16
17
18
GENERATOR RUN SIGNAL
GENERATOR BATTERY
|
|
| 5A fuse | STOP |
|
|
| ||
|
|
| ||
|
|
| 5A fuse | START |
|
|
| ||
|
|
| ||
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
For additional information, see “Circuit Limitations” on page
Figure 2-14 Type 10 Connection Diagram
Table 2-13 Type 10 Relay and Timing Preset Configurations
Relay Function | Preset Configuration Setting |
|
|
Relay 1 mode | StartStop |
|
|
Relay 3 mode | No function |
|
|
Gen Run signal hold time | 0.5 s |
|
|
Preheat time | 0 s |
|
|
Preheat to crank delay | 0 s |
|
|
Crank time | 15 s |
|
|
Crank retry time | 30 s |
|
|
Gen Cool Down | 30 s |
|
|
Shutdown bypass time | 0 s |
|
|
Start tries | 3 |
|
|