Installing the XW Automatic Generator Start

Type 1

Type 1 is a three-wire GlowStop configuration recommended for “three- wire” generators with glow plugs that need to be operated before a start is attempted.

XW AGS Harness Wires

12

13

Relay 1

14

5A fuse

16

 

 

 

Relay 2

17

5A fuse

18

 

 

 

Generator Wires

GENERATOR RUN SIGNAL GENERATOR BATTERY NEGATIVE(–) PREHEAT

START

For additional information, see “Circuit Limitations” on page 2–5.

Figure 2-3

Type 1 Connection Diagram

Table 2-4

Type 1 Relay and Timing Preset Configurations

Relay Function

 

Preset Configuration Setting

 

 

 

 

 

Relay 1 mode

 

GlowStop

 

 

 

 

Relay 3 mode

 

No function

 

 

 

 

Gen Run signal hold time

 

0.5 s

 

 

 

 

Preheat time

 

20 s

 

 

 

 

Preheat to crank delay

 

1 s

 

 

 

 

 

Crank time

 

 

15 s

 

 

 

 

Crank retry time

 

30 s

 

 

 

 

Gen Cool Down

 

30 s

 

 

 

 

Shutdown bypass time

 

0 s

 

 

 

 

 

Start tries

 

 

3

 

 

 

 

 

 

975-0307-01-01

2–9

Page 31
Image 31
Xantrex Technology XW manual Type