Installation

Installing the XW Automatic Generator Start

Installation Overview

Installing the XW Auto Generator Start involves the following steps:

1.Mounting the unit.

2.Connecting the wiring harness to:

the generator (page 2–8)

thermostats (optional) (page 2–22)

external shutdown switch (optional) (page 2–22)

external ON/OFF switch and LED (optional) (page 2–23)

3.Connecting the wiring harness to the 20-contact connector on the XW Auto Generator Start.

4.Connecting the XW Auto Generator Start to the XW System Control Paneland other network-enabled devices (page 2–26).

Important: Because each installation varies according to the location, the type of generator, and the overall complexity of the Xanbus system, these instructions can offer only general guidelines for the many installation options available.

WARNING: Shock Hazard

Before installing the XW Auto Generator Start as part of a pre-existing Xanbus system, put the system in Standby in order to disable the electrical operation of networked devices. See “Putting the XW Auto Generator Start in Standby Mode” on page 4–6.

Mounting the Unit

The XW Auto Generator Start is to be mounted vertically on a wall with the connectors facing downwards.

To mount the XW Auto Generator Start:

1.Hold the unit flush and square against the wall, panel, or horizontal surface.

If the mounting surface requires pre-drill holes for the screws, use the supplied mounting template to mark, then drill, four holes.

2.With a Phillips screwdriver and the supplied #6 screws, secure each corner of the XW Auto Generator Start to the mounting surface.

2–4

975-0307-01-01

Page 26
Image 26
Xantrex Technology manual Installing the XW Automatic Generator Start, Mounting the Unit