Xantrex Technology XW manual 13 Type 9 Connection Diagram

Models: XW

1 124
Download 124 pages 55.26 Kb
Page 39
Image 39
Figure 2-13Type 9 Connection Diagram

Installing the XW Automatic Generator Start

Type 9

Type 9 is a StartStop mode configuration with shutdown bypass functionality on relay 3. This configuration is intended for Westerbeke generators.

XW AGS Harness Wires

Generator Wires

Relay 1

Relay 2

12

13

14

16

17

18

 

 

 

 

GENERATOR RUN SIGNAL

 

 

 

 

 

 

 

 

GENERATOR BATTERY NEGATIVE(–)

 

 

 

5A fuse

 

 

 

STOP

 

 

 

 

 

 

 

 

 

 

 

5A fuse

START

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

19

5A fuse FUEL PRIME (PREHEAT)

Relay 3

12V GENERATOR BATTERY+

20

For additional information, see “Circuit Limitations” on page 2–5.

Figure 2-13Type 9 Connection Diagram

Table 2-12Type 9 Relay and Timing Preset Configurations

Relay Function

Preset Configuration Setting

 

 

Relay 1 mode

StartStop

 

 

Relay 3 mode

Shutdown Bypass

 

 

Gen Run signal hold time

0.5 s

 

 

Preheat time

0 s

 

 

Preheat to crank delay

0 s

 

 

Crank time

15 s

 

 

Crank retry time

30 s

 

 

Gen Cool Down

30 s

 

 

Shutdown bypass time

5 s

 

 

Start tries

3

 

 

975-0307-01-01

2–17

Page 39
Image 39
Xantrex Technology XW manual 13 Type 9 Connection Diagram, 12 Type 9 Relay and Timing Preset Configurations