Xantrex Technology XW manual The Configuration Menu, QT En

Models: XW

1 124
Download 124 pages 55.26 Kb
Page 57
Image 57
The Configuration Menu

The XW Auto Gen Start Menu

The Configuration Menu

The Configuration Menu is where specific start-stop parameters are set.

This menu contains the following settings:

QT EN

QT Begin

QT END

Gen Type

Cfg Trigger

Cfg Gen

Multi-unit Config

Restore Defaults

QT En

Full name

Quiet Time Enable

 

 

Purpose

“QT En” enables or disables the Quiet Time functionality of the XW Auto

 

Generator Start. Quiet time refers to a period of time when the generator

 

should not run.

 

 

Dependencies

“QT En” requires the XW Auto Generator Start to be in Automatic mode.

 

Setting “QT En” to [Enable] requires that parameters be set for the “QT

 

Begin” and “QT End”.

 

 

 

Value

 

Description

 

 

 

 

 

 

 

Enabled/Disabled

 

Enables or disables the Quiet Time functionality.

 

 

 

 

When to use

Set “QT En” to [Enabled] when there is a period of time when it is not

 

desired for the generator to run. The XW Auto Generator Start will ignore

 

all automatic start triggers during the time set in “QT Begin” and “QT

 

Begin”.

 

 

 

When there are no preferences or restrictions for when the generator

 

should run, set “QT En” to [Disabled]. When [Disabled] is selected, the

 

XW Auto Generator Start will ignore the times set for “QT Begin” and

 

“QT End”.

 

 

Considerations

Quiet Time prevents the automatic starting of the generator regardless of

 

battery condition.

 

 

975-0307-01-01

3–7