Xantrex Technology XW manual Figure C-2 MomentaryRun Mode Timing Diagram

Models: XW

1 124
Download 124 pages 55.26 Kb
Page 111
Image 111
MomentaryRun Mode

MomentaryRun Mode

MomentaryRun Mode

For generators with MomentaryRun mode starting types (Type 11):

Relay 1 (Run/Stop relay) can be used for two-wire configured generators.

Relay 2 has no unique function in this configuration, but it is easiest to leave it doing the cranking so that another configuration is not required for it.

Preheat will generally not be used in this configuration.

The Preheat will never overlap the Crank Time.

The “Delay” refers to the “Preheat to Crank Delay” and may be zero.

Cranking will cease when the generator run signal goes high for the specified hold time or when the crank time has elapsed.

Figure C-2MomentaryRun Mode Timing Diagram

975-0307-01-01

C–3

Page 111
Image 111
Xantrex Technology XW manual Figure C-2 MomentaryRun Mode Timing Diagram