Start DCV 30 sec

Configuration

Start DCV 30 sec

Full Name

Starting Battery Voltage—30 seconds

 

 

 

Purpose

The “Start DCV 30 sec” trigger enables the XW Auto Generator Start to

 

start the generator whenever the battery voltage reaches or drops below a

 

pre-set voltage for longer than 30 seconds.

 

 

 

 

The XW Auto Generator Start will stop the generator when the stop

 

trigger is provided (“Stop V”, “Stop Absorb”, or “Stop Float”).

Dependencies

The “Start DCV 30 sec” trigger requires the XW Auto Generator Start to

 

be in Automatic mode and needs the “Stop Absorb” or “Stop Float”

 

trigger be enabled or a parameter to be set for the “Stop V” trigger.

 

Values

 

Default

 

 

 

 

 

 

 

 

Disabled, 4.0 V to 65.0 V(increments of 0.1 V)

 

44.0 V

 

 

 

 

 

Considerations

If the voltage trigger is set too high, the generator will start more

 

frequently than is convenient.

 

 

 

 

If the voltage trigger is set too low, the batteries may be damaged by

 

repeated cycles of excessive discharge. The generator running time

 

necessary to charge the batteries may exceed “Max Run Time” and use

 

too much fuel in the process.

 

 

 

 

If using the XW Inverter/Charger Low Batt Cut Out voltage setting to

 

trigger a start-on-voltage setting on the XW Auto Generator Start, be sure

 

to set the XW Auto Generator Start voltage trigger higher than the XW

 

Inverter/Charger Low Batt Cut out voltage. Otherwise the inverter output

 

turns off and then back on when the generator auto-starts.

 

If using an automatic generator starting system with the start trigger set to

 

the same voltage as the LBCO voltage, do not set the LBCO Delay for

 

less than the amount of time it takes the generator to start and connect.

 

Otherwise, inverter output turns off and then back on when the generator

 

auto-starts.

 

 

 

Battery Voltage

Battery voltage can be monitored from the System screen or the inverter/

Information

charger menu.

 

 

 

If “Stop Float” or “Stop Absorb” has been enabled, the generator will stop when the Float or Absorption stages of the battery charging have begun.

If the “Stop V” is used, the generator will stop when the battery voltage reaches the parameter set in this trigger, regardless of whether the batteries are charged.