Installing the XW Automatic Generator Start
Type 11
Type 11 is a
XW AGS Harness Wires |
| Generator Wires | ||||||
| 12 |
|
|
|
|
| GENERATOR RUN SIGNAL | |
|
|
|
|
|
| |||
| 13 |
|
|
|
|
| GENERATOR BATTERY | |
|
|
|
|
|
| |||
Relay 1 |
| 14 |
|
|
|
| 5A fuse | RUN |
|
|
|
| |||||
|
|
|
| |||||
16 |
|
|
|
|
|
| ||
|
|
|
|
|
| |||
|
|
|
|
|
|
|
For additional information, see “Circuit Limitations” on page
Figure 2-15 Type 11 Connection Diagram
Table 2-14 Type 11 Relay and Timing Preset Configurations
Relay Function | Preset Configuration Setting |
|
|
Relay 1 mode | MomentaryRun |
|
|
Relay 3 mode | No function |
|
|
Gen Run signal hold time | 0.5 s |
|
|
Preheat time | 0 s |
|
|
Preheat to crank delay | 0 s |
|
|
Crank time | 10 s |
|
|
Crank retry time | 15 s |
|
|
Gen Cool Down | 30 s |
|
|
Shutdown bypass time | 0 s |
|
|
Start tries | 3 |
|
|