Installing the XW Automatic Generator Start

Type 11

Type 11 is a two-wire run mode configuration intended for Kohler generators. It requires only two wires and one relay to control the generator. Relay 1 closes momentarily once to start the generator, and closes momentarily again to stop the generator.

XW AGS Harness Wires

 

Generator Wires

 

12

 

 

 

 

 

GENERATOR RUN SIGNAL

 

 

 

 

 

 

 

13

 

 

 

 

 

GENERATOR BATTERY NEGATIVE(–)

 

 

 

 

 

 

Relay 1

 

14

 

 

 

 

5A fuse

RUN

 

 

 

 

 

 

 

 

16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

For additional information, see “Circuit Limitations” on page 2–5.

Figure 2-15Type 11 Connection Diagram

Table 2-14Type 11 Relay and Timing Preset Configurations

Relay Function

Preset Configuration Setting

 

 

Relay 1 mode

MomentaryRun

 

 

Relay 3 mode

No function

 

 

Gen Run signal hold time

0.5 s

 

 

Preheat time

0 s

 

 

Preheat to crank delay

0 s

 

 

Crank time

10 s

 

 

Crank retry time

15 s

 

 

Gen Cool Down

30 s

 

 

Shutdown bypass time

0 s

 

 

Start tries

3

 

 