| Installing the XW Automatic Generator Start | |
|
|
|
|
|
| Table | Contact Numbers and Functions |
| |
|
|
|
| |
| Wire |
|
| Wiring Harness |
| Number |
| Function | Wire Color |
|
|
|
|
|
1 |
| Thermostat 1 input | Yellow | |
|
|
|
|
|
2 |
| Thermostat 1 return | Gray | |
|
|
|
|
|
3 |
| Thermostat 2 input | Orange | |
|
|
|
|
|
4 |
| Thermostat 2 return | Gray | |
|
|
|
|
|
5 |
| External shutdown input | White/Black | |
|
|
|
|
|
6 |
| External shutdown return | Gray | |
|
|
|
|
|
7 |
| External manual on input | White/Green | |
|
|
|
|
|
8 |
| External manual off input | White/Red | |
|
|
|
|
|
9 |
| External ON/OFF LED Indicator output | White/Blue | |
|
|
|
|
|
10 |
| Constant 12/24 V B+ (battery positive) for | Red | |
|
|
| External ON/OFF/LED Indicator |
|
|
|
|
|
|
11 |
| External ON/OFF/LED Indicator return | Black | |
|
|
| (connected internally to wire number 13) |
|
|
|
|
|
|
12 |
| Generator run signal (switched B+) sense input | Violet | |
|
|
|
|
|
13 |
| Generator run signal (switched B+) sense return | Black | |
|
|
| (generator battery negative) |
|
|
|
|
|
|
14 |
| Relay 1 (Generator run/stop) Normally open | Blue | |
|
|
| contact |
|
|
|
|
|
|
15 |
| Relay 1 (Generator run/stop) Normally closed | White/Violet | |
|
|
| contact |
|
|
|
|
|
|
16 |
| Relay 1 (Generator run/stop) Common contact | Gray | |
|
|
|
|
|
17 |
| Relay 2 (Generator start) Normally open contact | White | |
|
|
|
|
|
18 |
| Relay 2 (Generator start) Common contact | Gray | |
|
|
|
|
|
19 |
| Relay 3 (Preheat/cooldown) Normally open | Brown | |
|
|
| contact |
|
|
|
|
|
|
20 |
| Relay 3 (Preheat/cooldown) Common contact | Gray | |
|
|
|
|
|