| The XW Auto Gen Start Menu | ||
|
|
|
|
| |
Dependencies | The “Exercise Per” trigger requires parameters to be set in the “Exercise | ||||
| Dur” and “Exercise Time” menu items. |
|
|
|
|
| Values |
|
| Default | |
|
|
| |||
|
|
|
|
| |
| 0 (Off), 1day to 250days (increments of 1day) | 21days | |||
|
|
|
|
| |
Considerations | Generators need to run regularly in order to maintain mechanical health | ||||
| and performance. If the generator isn’t needed and doesn’t run, it is | ||||
| recommended that an Exercise period be set to keep the generator in good | ||||
| working condition. |
|
|
|
|
| If the generator runs frequently throughout the year, it may not need to set | ||||
| an exercise period. In that case, set the “Exercise Per” trigger to 0. | ||||
|
|
|
| ||
| Important: Consult the generator manual or a service representative from the | ||||
| generator’s manufacturer for the recommended exercise period. | ||||
Exercise Dur |
|
|
|
|
|
Full name | Exercise Duration (in minutes) |
|
|
|
|
Purpose | “Exercise Dur” sets how long the generator will run when it is exercised. | ||||
Dependencies | The “Exercise Dur” trigger requires that any parameter other than “0” be | ||||
| set in “Exercise Per” and a time of day be set in the “Exercise Time” | ||||
| trigger. |
|
|
|
|
| Values |
| Default | ||
|
| ||||
|
|
|
|
| |
| 1min to 250min |
| 30min | ||
|
|
|
|
|
|
Important: Ensure that the Exercise Duration is not set for longer than the “Max Run Time” setting. Attempting to do so will generate a warning on the System Control Panel.
Important: Consult the generator manual or a service representative from the generator’s manufacturer for the recommended exercise duration.