Installing the XW Automatic Generator Start

Type 3

Type 3 is a three-wire GlowStop with shutdown bypass configuration. The configuration shown in Figure 2-5 uses a shutdown bypass output to temporarily disable the generator’s low oil pressure shutdown functionality during cranking. Generators with this functionality often have a manual means of disabling it during cranking.

XW AGS Harness Wires

Generator Wires

12

13

14

Relay 1

16

Figure 2-5Type 3 Connection DiagramTable 2-6Type 3 Relay and Timing Preset Configurations 17

Relay 2

18

5A fuse

5A fuse

GENERATOR RUN SIGNAL GENERATOR BATTERY NEGATIVE(–)

PREHEAT STOP

BYPASS SHUTDOWN START

For additional information, see “Circuit Limitations” on page 2–5.

Figure 2-5Type 3 Connection Diagram

Table 2-6Type 3 Relay and Timing Preset Configurations

Relay Function

Preset Configuration Setting

 

 

Relay 1 mode

GlowStop/Shutdown bypass

 

 

Relay 3 mode

Preheat/Shutdown bypass

 

 

Gen Run signal hold time

0.5 s

 

 

Preheat time

20 s

 

 

Preheat to crank delay

0 s

 

 

Crank time

15 s

 

 

Crank retry time

30 s

 

 

Gen Cool Down

30 s

 

 

Shutdown bypass time

10 s

 

 

Start tries

3

 

 