Installing the XW Automatic Generator Start
Type 5
Type 5 is a
XW AGS Harness Wires | Generator Wires |
Relay 1
Relay 2
12
13
14
16
17
18
|
|
|
| GENERATOR RUN SIGNAL |
|
|
|
| |
|
|
|
| GENERATOR BATTERY |
|
|
| 5A fuse | |
|
|
| STOP/PREHEAT | |
|
|
| ||
|
| |||
|
|
| ||
|
|
| 5A fuse | START |
|
|
| ||
|
|
| ||
|
|
|
| |
|
|
|
|
|
19 | 5A fuse FUEL PRIME (PREHEAT) |
Relay 3 | 12V GENERATOR BATTERY+ |
20 |
For additional information, see “Circuit Limitations” on page
Figure 2-7 Type 5 Connection Diagram
Table 2-8 Type 5 Relay and Timing Preset Configurations
Relay Function | Preset Configuration Setting |
|
|
Relay 1 mode | StartStop |
|
|
Relay 3 mode | Preheat |
|
|
Gen Run signal hold time | 2 s |
|
|
Preheat time | 15 s |
|
|
Preheat to crank delay | 2 s |
|
|
Crank time | 15 s |
|
|
Crank retry time | 15 s |
|
|
Gen Cool Down | 30 s |
|
|
Shutdown bypass time | 0 s |
|
|
Start tries | 3 |
|
|