| Warning Messages |
|
|
|
|
|
|
|
Table | XW Auto Generator Start Warning Messages(Continued) |
| |||
|
|
|
|
|
|
Warning |
| Self- |
|
|
|
Number | Message | clearing? | Cause | Action |
|
|
|
|
|
|
|
W250 | The selected value | No | You have tried to change | Put the system into |
|
| failed to change. |
| the Gen Type without | Standby, change the Gen |
|
| Try again. |
| putting the system into | Type, then return the |
|
|
|
| Standby first. | system to Operating mode. |
|
|
|
|
|
|
|
|
|
| You have tried to set the | Ensure that “Max Run |
|
|
|
| “Exercise Dur” for longer | Time” is set for longer than |
|
|
|
| than “Max Run Time,” or | “Exercise Dur.” |
|
|
|
| “Max Run Time” for less |
|
|
|
|
| than “Exercise Dur.” |
|
|
|
|
|
|
|
|
W500 | Network | Yes | The XW Auto Generator | Check connection between |
|
| connection lost. |
| Start has lost | the XW Auto Generator |
|
| Check connections. |
| communications with the | Start and the network. |
|
|
|
| network because of a faulty |
|
|
|
|
| connection or electronic |
|
|
|
|
| signal disruption. |
|
|
|
|
|
|
|
|
W501 | XW Auto | No | The XW Auto Generator | Acknowledge the warning |
|
| Generator Start has |
| Start encountered an | and reset configurable |
|
| fixed memory |
| internal memory problem | settings if necessary. |
|
| problem and |
| upon startup. To remain |
|
|
| restored default |
| operational, the XW Auto |
|
|
| settings. |
| Generator Start restored its |
|
|
|
|
| default settings. |
|
|
|
|
|
|
|
|