Configuration

User Settings

Use this table to record any customized XW Auto Generator Start settings for future reference.

Table 3-3Generator Configuration Settings, Values, Defaults, and User Settings

 

 

 

 

User

Setting

 

Values

Default

Setting

 

 

 

 

 

Main Menu Items:

 

 

 

 

 

 

 

GenMode

 

ManualOn, ManualOff, Automatic

ManualOff

 

 

 

 

 

 

Mode

 

Operating/Standby

Operating

 

 

 

 

 

Configuration Menu Items:

 

 

 

 

 

 

“QT En”

 

Enabled, Off

Enabled

 

 

 

 

 

 

“QT Begin”

 

12:00AM–11:59PM (12-hour clock)

9:00PM (12-hour clock)

 

 

 

00:00–23:59 (24-hour clock)

21:00 (24-hour clock)

 

 

 

 

 

 

“QT End”

 

12:00AM–11:59PM (12-hour clock)

8:00AM (12-hour clock)

 

 

 

00:00–23:59 (24-hour clock)

8:00 (24-hour clock)

 

 

 

 

 

 

“Gen Type”

 

Type 1 to Type 13

Type 2

 

 

 

 

 

 

Triggers Menu Items:

 

 

 

 

 

 

 

“Start DCV 30 sec”

 

Disabled, 4.0 V–65.0 V

44.0 V

 

 

 

 

 

 

“Start DCV 15 min”

 

Disabled, 4.0 V–65.0 V

Disabled

 

 

 

 

 

 

“Start DCV 2 hr”

 

Disabled, 4.0 V–65.0 V

Disabled

 

 

 

 

 

 

“Start DCV 24 hr”

 

Disabled, 4.0 V–65.0 V

Disabled

 

 

 

 

 

 

“Stop Float”

 

Enabled, Disabled

Disabled

 

 

 

 

 

 

“Stop Absorb”

 

Enabled, Disabled

Enabled

 

 

 

 

 

 

“Stop V”

 

Disabled, 4.0 V–65.0 V

Disabled

 

 

 

 

 

 

“Temp1”

 

Enabled, Disabled

Disabled

 

 

 

 

 

 

“Temp2”

 

Enabled, Disabled

Disabled

 

 

 

 

 

 

“Load”

 

Enabled, Disabled

Disabled

 

 

 

 

 

 

“Start Load”

 

10.0 A–33.0 A

10.0 A

 

 

 

 

 

 

“Stop Load”

 

7.0 A–28.0 A

7.0 A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3–32

975-0307-01-01

Page 82
Image 82
Xantrex Technology XW manual User Settings