Max Run Time

Configuration

Max Run Time

Full name

Maximum Generator Run Time

 

 

Purpose

“Max Run Time” allows a limit to be set on how long the generator will

 

run. This setting overrides any automatic start triggers. For example, if

 

the generator starts in response to low battery voltage, and the batteries

 

are not fully charged before “Max Run Time” is reached, the generator

 

will stop. In addition, when the generator is started manually from the

 

XW System Control Panel, the generator will stop when “Max Run Time”

 

is reached.

 

 

 

When started with an external manual ON/OFF switch, the generator will

 

not stop when it reaches “Max Run Time”. The generator must be stopped

 

with the external manual ON/OFF switch, or by using the System Control

 

Panel to change the “GenMode” to ManualOff.

 

If the XW Auto Generator Start reaches “Max Run Time”, a warning

 

message will appear on the XW System Control Panel. The XW Auto

 

Generator Start will stop operating until the warning is acknowledged by

 

pressing ENTER on the XW System Control Panel.

 

Values

 

Default

 

 

 

 

 

 

 

0 hours to 24 hours (increments of 1hour)

 

8 hours

 

 

 

 

Considerations

Adjust the “Max Run Time” if the maximum generator run time:

 

• exceeds the fuel capacity of the generator, or

 

• is not long enough to fully recharge the batteries under optimum

 

conditions.

 

 

Exercise Per

 

 

 

Full name

Set Exercise Period (in days).

 

 

Purpose

“Exercise Per” sets the minimum time interval between each running of

 

the generator. If the generator has not been run within this time frame, the

 

XW Auto Generator Start will start the generator to “exercise” it.

The time interval defined by the Exercise Period setting begins with the last time the generator was run for any reason, not with the last time the XW Auto Generator Start exercised the generator.

For example, setting an exercise period of 30 days would start the generator if it had not been run at all for 30 days.

3–22

975-0307-01-01