Configuration
Generator | This generator name is used by the XW inverter/charger to identify which |
| generator is connected to the AC2 input. It is only necessary to change |
| this setting in installations with more than one XW Auto Generator Start |
| in a system. In this case, the “generator” name on each XW Auto |
| Generator Start will have to be unique. |
| Example: If a generator is connected to AC2 on an XW inverter/charger, |
| the generator name (e.g., Gen1, Gen2 etc.) selected for AC2 under |
| “Connections” on the XW must match the generator name assigned here. |
| See the XW Inverter/Charger Operator’s Guide for additional |
| information. |
Restore Defaults
The “Restore Defaults” returns the XW Auto Generator Start to the factory default settings.
GenMode
Purpose | The GenMode menu item controls the current operating mode of the XW | ||
| Auto Generator Start. | ||
| Value |
| Description |
|
| ||
|
|
|
|
| Automatic |
| Automatic mode |
|
|
|
|
| ManualOn |
| Manual on mode |
|
|
|
|
| ManualOff |
| Manual off mode (default mode) |
|
|
|
|
Considerations | Use GenMode when it is necessary to switch between automatic | ||
| generator control and manual generator control. |
When the Xanbus system powers up all
Automatic Mode
To have the XW Auto Generator Start start and stop the generator automatically, select Automatic. The generator can start and stop automatically in response to low battery voltage, AC loads on the inverter, thermostat triggers, or exercise time. Automatic mode also has a Quiet