The XW Auto Gen Start Menu

 

 

 

 

 

 

 

 

QT End

 

 

 

 

 

 

Full name

 

Quiet Time End

 

 

 

 

Purpose

 

“QT End” is a changeable setting that defines the end of quiet time.

 

 

 

This setting also requires a setting for “QT Begin”.

 

Dependencies

“QT End” functions only if the XW Auto Generator Start is in Automatic

 

 

 

mode. This setting requires “QT En” be set to [Enabled] and also requires

 

 

 

a setting for the “QT Begin” trigger. This setting is triggered by the

 

 

 

setting on the system clock, so ensure the clock on the XW System

 

 

 

Control Panel is set to the correct local time.

 

 

 

Value

 

Description

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12:00AM to 11:59PM

 

At the time set for “QT End” the XW Auto

 

 

 

(12-hour clock)

 

Generator Start will be able to automatically start the

 

 

 

00:00 to 23:59

 

generator again. If a start trigger has occurred during

 

 

 

(24-hour clock)

 

quiet time and is still active, the generator will start

 

 

 

 

 

immediately after quiet time ends.

 

Gen Type

 

 

 

 

 

 

 

 

 

 

 

 

Full name

 

Generator Type

 

 

 

 

Purpose

 

“Gen Type” is a changeable setting for selecting the starting requirements

 

 

 

of the generator. The starting requirements determine how the XW Auto

 

 

 

Generator Start must be wired to the generator’s starting system. For more

 

 

 

information, see “Connecting the Generator” on page 2–8 or Appendix B.

 

 

 

 

 

 

 

 

 

Important: “Gen Type” can only be changed after the system is put into

 

 

 

Standby. See “Putting the XW Auto Generator Start in Standby Mode” on

 

 

 

page 4–6.

 

 

 

 

Table 3-1

Generator Type Descriptions and Examples

 

 

 

Description

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

For Technical

 

 

Option

Mode

 

 

Details, see...a

Examples of Generatorsb

 

 

 

 

 

 

 

Type 1

GlowStop

 

page 2–9

Generac

 

 

 

 

 

 

 

Type 2

GlowStop with no preheat

 

page 2–10

Onan Diesel (Default)

 

 

 

 

 

 

 

Type 3

GlowStop with shutdown bypass

 

page 2–11

Generac

 

 

 

 

 

 

 

Type 4

StartStop with Relay 3 prime

 

page 2–12

Guardian/Generac Gas

 

 

 

 

 

 

 

Type 5

StartStop with Relay 3 preheat

 

page 2–13

Guardian/Generac Diesel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

975-0307-01-01

3–9

Page 59