| The XW Auto Gen Start Menu |
|
|
|
|
|
|
|
|
QT End |
|
|
|
|
|
|
Full name |
| Quiet Time End |
|
|
|
|
Purpose |
| “QT End” is a changeable setting that defines the end of quiet time. |
| |||
|
| This setting also requires a setting for “QT Begin”. |
| |||
Dependencies | “QT End” functions only if the XW Auto Generator Start is in Automatic |
| ||||
|
| mode. This setting requires “QT En” be set to [Enabled] and also requires |
| |||
|
| a setting for the “QT Begin” trigger. This setting is triggered by the |
| |||
|
| setting on the system clock, so ensure the clock on the XW System |
| |||
|
| Control Panel is set to the correct local time. |
| |||
|
| Value |
| Description |
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| 12:00AM to 11:59PM |
| At the time set for “QT End” the XW Auto |
| |
|
|
| Generator Start will be able to automatically start the |
| ||
|
| 00:00 to 23:59 |
| generator again. If a start trigger has occurred during |
| |
|
|
| quiet time and is still active, the generator will start |
| ||
|
|
|
| immediately after quiet time ends. |
| |
Gen Type |
|
|
|
|
|
|
|
|
|
|
|
| |
Full name |
| Generator Type |
|
|
|
|
Purpose |
| “Gen Type” is a changeable setting for selecting the starting requirements |
| |||
|
| of the generator. The starting requirements determine how the XW Auto |
| |||
|
| Generator Start must be wired to the generator’s starting system. For more |
| |||
|
| information, see “Connecting the Generator” on page |
| |||
|
|
|
|
|
| |
|
| Important: “Gen Type” can only be changed after the system is put into |
| |||
|
| Standby. See “Putting the XW Auto Generator Start in Standby Mode” on |
| |||
|
| page |
|
|
|
|
Table | Generator Type Descriptions and Examples |
|
| |||
| Description |
|
|
|
| |
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
| For Technical |
|
|
Option | Mode |
|
| Details, see...a | Examples of Generatorsb |
|
|
|
|
|
|
| |
Type 1 | GlowStop |
| page | Generac |
| |
|
|
|
|
|
| |
Type 2 | GlowStop with no preheat |
| page | Onan Diesel (Default) |
| |
|
|
|
|
|
| |
Type 3 | GlowStop with shutdown bypass |
| page | Generac |
| |
|
|
|
|
|
| |
Type 4 | StartStop with Relay 3 prime |
| page | Guardian/Generac Gas |
| |
|
|
|
|
|
| |
Type 5 | StartStop with Relay 3 preheat |
| page | Guardian/Generac Diesel |
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|