Configuration
Start DCV 2 hr
Full name | Starting Battery | ||
Purpose | The “Start DCV 2 hr” trigger enables the XW Auto Generator Start to | ||
| start the generator whenever the battery voltage reaches or drops below a | ||
| |||
Dependencies | The “Start DCV 2 hr” trigger requires the XW Auto Generator Start to be | ||
| in Automatic mode and needs the “Stop Absorb” or “Stop Float” trigger | ||
| be enabled or a parameter to be set for the “Stop V” trigger. | ||
| Values |
| Default |
|
| ||
|
|
|
|
| Disabled, 4.0 V to 65.0 V |
| Disabled |
|
|
|
|
Considerations | If the voltage trigger is set too high, the generator will start more | ||
| frequently than is convenient. |
|
|
| If the voltage trigger is set too low, the batteries may be damaged by | ||
| repeated cycles of excessive discharge. The generator running time | ||
| necessary to charge the batteries may exceed “Max Run Time” and use | ||
| too much fuel in the process. |
|
|
Battery Voltage | Battery voltage can be monitored from the System screen or the inverter/ | ||
Information | charger menu. |
|
|
If “Stop Float” or “Stop Absorb” has been enabled, the generator will stop when the Float or Absorption stages of the battery charging have begun.
If the “Stop V” is used, the generator will stop when the battery voltage reaches the parameter set in this trigger, regardless of whether the batteries are charged.