Configuration

Start DCV 2 hr

Full name

Starting Battery Voltage—2 hours

Purpose

The “Start DCV 2 hr” trigger enables the XW Auto Generator Start to

 

start the generator whenever the battery voltage reaches or drops below a

 

pre-set voltage for longer than 2 hours.

Dependencies

The “Start DCV 2 hr” trigger requires the XW Auto Generator Start to be

 

in Automatic mode and needs the “Stop Absorb” or “Stop Float” trigger

 

be enabled or a parameter to be set for the “Stop V” trigger.

 

Values

 

Default

 

 

 

 

 

 

 

Disabled, 4.0 V to 65.0 V

 

Disabled

 

 

 

 

Considerations

If the voltage trigger is set too high, the generator will start more

 

frequently than is convenient.

 

 

 

If the voltage trigger is set too low, the batteries may be damaged by

 

repeated cycles of excessive discharge. The generator running time

 

necessary to charge the batteries may exceed “Max Run Time” and use

 

too much fuel in the process.

 

 

Battery Voltage

Battery voltage can be monitored from the System screen or the inverter/

Information

charger menu.

 

 

If “Stop Float” or “Stop Absorb” has been enabled, the generator will stop when the Float or Absorption stages of the battery charging have begun.

If the “Stop V” is used, the generator will stop when the battery voltage reaches the parameter set in this trigger, regardless of whether the batteries are charged.