Installing the XW Automatic Generator Start
Wiring to the 20-contact Connector
|
| CAUTION: Shock Hazard |
|
|
|
| All installation wiring should be performed by a qualified installer or electrician. | ||
|
|
|
| |
|
| WARNING: Fire, Shock, and Energy Hazards | ||
|
| The | ||
|
| Voltage) circuits only. Do not exceed the circuit limitations specified in the | ||
|
| following section. |
|
|
|
|
|
| |
ELV Circuits | ELV | |||
|
| more than 30 Vrms or 42.2 VDC or peak, and are therefore not a shock | ||
|
| hazard. |
|
|
Class 2 Circuits | As per the US National Electrical Code (NEC) and the Canadian | |||
|
| Electrical Code (CEC), available power in Class 2 circuits is limited to | ||
|
| 100 VA, usually by current limiting by means of overcurrent protection or | ||
|
| series resistance. The current is limited to 5 A for circuits with open- | ||
|
| circuit voltage of 20 V, and to I=100/Voc for circuits with open circuit | ||
|
| voltage between 20 V and 30 V. |
|
|
Circuit | The relay contacts in the XW Auto Generator Start are rated at 5 A | |||
Limitations | maximum and all circuits on the | |||
|
| maximum. |
|
|
|
| Ensure that all circuits connected to the | ||
|
| the following limits: |
|
|
|
| Table |
|
|
|
| Circuit Parameter |
| Circuit Maximum |
|
|
| ||
|
|
|
|
|
|
| Open circuit voltage (Voc) |
| 30 V maximum |
|
|
|
|
|
|
| Overcurrent protection |
| 5 A maximum |
|
| (fuse size for open circuit voltage up to 20 V) |
|
|
|
|
|
|
|
|
| Overcurrent protection |
| 5 A to 3.33 A |
|
| (fuse size for open circuit voltage from 20 V to 30 V) |
| (100/Voc amps |
|
|
|
| maximum) |
|
|
|
| |
Wiring Harness | Connections to the generator, thermostats, and external ON/OFF switches | |||
|
| are made using a wiring harness that plugs into the | ||
|
| (see Figure |
|
|