Xantrex Technology XW manual 4 Type 2 Connection Diagram, Generator Wires

Models: XW

1 124
Download 124 pages 55.26 Kb
Page 32
Image 32
Generator Wires

Installation

Type 2

Type 2 is a three-wire GlowStop configuration recommended for “three- wire” generators that don’t require a dedicated preheat signal, such as Onan generators. In this configuration, the start signal is applied for longer because the generator does its own preheat and cranking while the start signal is applied.

XW AGS Harness Wires

Generator Wires

Relay 1

12

13

14

16

GENERATOR RUN SIGNAL

GENERATOR BATTERY NEGATIVE(–)

5A fuse

RUN

Relay 2

17

18

 

 

 

5A fuse

START

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

For additional information, see “Circuit Limitations” on page 2–5.

Figure 2-4Type 2 Connection Diagram

Table 2-5Type 2 Relay and Timing Preset Configurations

Relay Function

Preset Configuration Setting

 

 

Relay 1 mode

GlowStop

 

 

Relay 3 mode

No function

 

 

Gen Run signal hold time

0.5 s

 

 

Preheat time

0 s

 

 

Preheat to crank delay

0 s

 

 

Crank time

30 s

 

 

Crank retry time

40 s

 

 

Gen Cool Down

30 s

 

 

Shutdown bypass time

0 s

 

 

Start tries

3

 

 

2–10

975-0307-01-01

Page 32
Image 32
Xantrex Technology XW manual 4 Type 2 Connection Diagram, 5 Type 2 Relay and Timing Preset Configurations, Generator Wires